PCA processing
The master controls and monitors VLT parameters
through the PCA portion of the PPOs type 1, 2 and
5 and requests a response from the VLT (slave). In
addition to the parameter processing, the VLT can
also transmit a spontaneous message.
Requests and responses involve an acknowledge-
ment exchange (a so-called handshake) which
cannot be worked off in stack operation. This
means that the master, when sending a read/write
request, must wait for the response before sending
a new request. A request or response is limited to
a maximum of 4 bytes, i.e. no text strings can be
transmitted.
PCA - Parameter description
15 14 13
12
11
10
R C
MSP
RC:
Request/Response Characteristics
SPM: Toggle bit for spontaneous messages
PNU: Parameter Number
Request and response
In the RC portion of the PCA word the requests of
the master to the slave are triggered. The other two
PCV fields IND and PVA must be evaluated as
well.
The PVA portion transmits parameter values in
word size with the bytes 7 and 8; double words
require the bytes 5-8, i.e. 32 bits.
If the request or response contains array elements,
the array subindex will be in IND (byte 3). In the
event of a parameter description, IND contains the
record subindex.
RC content
Request
Function
0
No request
1
Request parameter value
2
Change parameter value (word)
3
Change parameter value (double word)
4
Request description element
5
Change description element
6
Request parameter value (array)
7
Change parameter value (array word)
8
Change parameter value (array
double word)
9
Request number of array elements
10-15
Not assigned
MG.90.D1.02
– VLT is a registered Danfoss trademark
VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
9
8
7 6 5 4 3 2 1 0
PNU
(Sector: 0-15)
(Sector: 1-990)
Response
Function
0
No response
1
Transmit parameter value (word)
2
Transmit parameter value (double
word)
3
Transmit description element
4
Transmit parameter value (array word)
5
Transmit parameter value
(array double word)
6
Transmit number of array elements
7
Request not executable (with error
number, see below)
8
No operating authority for PCV inter-
face
9
Spontaneous message (word)
10
Spontaneous message (double word)
11
Spontaneous message (array word)
12
Spontaneous message (array double
word)
13-15
Not assigned
If a request from the master is not executed by the
slave, the RC word in the PPO-Read has the
value 7. The error number is in bytes 7 and 8 of the
PVA element.
Error no.
Meaning
0
Improper PNU
1
Parameter value not changeable
2
Upper or lower value passed
3
Faulty subindex
4
No array
5
Wrong data type
6
Setting not permitted (resettable only)
7
Description element not changeable
8
No PPO-Write for IR
9
Description data not available
10
Access group
11
No parameter operating authority
12
Keyword missing
13
Text not readable in cyclical traffic
14
Name not readable in cyclical traffic
15
Text array not available
16
PPO-Write missing
17
Request temporarily unexecutable
18
Other error
19
Data not readable in cyclical traffic