953 Warning messages (WARNING PARAM.)
Value
Read only (16 bit binary code)
No control panel access
Function
A bit is assigned to every warning (see the follo-
wing list).
Bit
In the following cases, bit is = "1":
0
LSB
Connection to the DP master is not
O K
1
Connection to the FMS master is
not OK
2
FDL (field bus data security layer)
is not OK
3
Command to erase data received
4
Current value not updated
5
FIFO overflow of the spontaneous
messages
6
PROFIBUS ASIC does not transmit
7
Initialization of the PROFIBUS
option is not OK
8
Not used
9
Not used
10
Not used
11
Not used
12
Not used
13
Not used
14
Not used
15
MSB
Not used
967 Control word (CONTROL WORD FMS)
Value
16 bit binary code
No control panel access
Function
Parameter 967 is dedicated to sending a control
word to the VLT when FMS with acyclical commu-
nication (without PPOs) is used. The dispatch of a
control word takes place through the FMS-Write
service to parameter 967 (Index 4967).
Factory settings
MG.90.D1.02
– VLT is a registered Danfoss trademark
VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
968 Status word (STATUS WORD FMS)
Value
Read only (16 bit binary code)
No control panel access
Function
Parameter 968 is dedicated to reading the status
word from the VLT when FMS with acyclical com-
munication or cyclical reading on KR 5 (without
PPOs) are used. The reading of the status word
takes place through the FMS-Read service from
parameter 968 (Index 4968).
970 Parameter setup selection
Value
Factory setting
Parameter setup 1 (SETUP1)
Parameter setup 2 (SETUP 2)
Parameter setup 3 (SETUP 3)
Parameter setup 4 (SETUP 4)
Active set up (ACTIVE SETUP)
Function
Like parameter 005 (described in the product ma-
nual for the VLT 5000 series).
971 Save data values (STORE DATA VALUE)
Value
Not active (OFF)
Save operations setup
(STORE ACTIVE SETUP)
Save program setup (STORE EDIT SETUP)
Save all setups (STORE ALL SETUPS)
Function
Parameter values modified through PROFIBUS are
only saved in RAM, i.e. the modifications are lost in
the event of a power failure. This parameter is
used to activate a function by means of which all
parameter values are saved in EEPROM, preser-
ving them even in the case of a power failure.
(EDIT SETUP SELECT)
[0]
[1]
[2]
[3]
[4]
[5]
[0]
[1]
[2]
[3]
35