Auto Start; Single Upm Shutdown - Eaton Powerware 9315 Installation And Operation Manual

Parallel capacity/redundant system
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

10.3.3

Auto Start

NOTE: Autorestart must be enabled to use this procedure.
1.
Perform the Initial Setup procedures.
2.
On SBM, turn the SYSTEM MODE key switch to BYPASS momentarily.
3.
Observe that CBP and FBP have closed.
4.
On all UPMs, set BATTERY switch to ENABLE.
5.
On SBM, turn the SYSTEM MODE key switch to NORMAL momentarily.
The UPS CB1 breakers close.
The rectifiers and input/rectifier cooling blowers turn on.
All CB2 (MBB) UPS battery breakers close.
NOTE: If CB2 is a manual battery breaker, manually close CB2 after UPM
Battery Disconnected alarm and notification is received.
All inverter and output/inverter cooling blowers turn on. When the inverters reach full
voltage, the UPS CB3 breakers close. It takes less than one minute for the UPMs to
achieve Normal mode.
The UPMs are now ready to supply power to the critical load.
6.
Once the Parallel Capacity/Redundant system is redundant, the critical load is
automatically transferred from bypass to the UPMs via the CBS breaker and
system is operating in Normal mode.
NOTE: If transfer is not completed within one minute, the SYSTEM MODE key
switch must be turned momentarily to NORMAL again to achieve normal
operation.
10.3.4

Single UPM Shutdown

NOTE: If system is not redundant, UPM cannot be shut down using this procedure.
1.
On UPM, turn the MODE key switch to BYPASS for three seconds.
2.
Verify that UPS breakers CB1 and CB3 and battery breaker CB2 (MBB) are
open and the UPM powers down.
3.
On SBM monitor screen, verify UPS OFF, message appears.
Power is present at UPM CB1 input until upstream UPM input
feeder circuit breaker is opened. The load side of CB3 still has
10−10
WARNING
voltage present.
EATON Powerware 9315 Parallel Capacity/Redundant System
164201150
Rev. E www.powerware.com
1