ABB PowerValue 31/11 T 10 kVA User Manual page 31

Table of Contents

Advertisement

for 100ms before UPS output is cut off.
Bypass voltage low
When the voltage in the bypass is below this
limit
limit, the UPS changes running mode.
Bypass voltage high
When the voltage in the bypass is above this
limit
limit, the UPS changes running mode.
Bypass frequency
When the frequency in the bypass is below
low limit
this limit, the UPS changes running mode.
Bypass frequency
When the frequency in the bypass is above
high limit
this limit, the UPS changes running mode.
Eco-mode voltage
When the voltage in the bypass is below this
low limit
limit, the UPS changes running mode.
Eco-mode voltage
When the voltage in the bypass is above this
high limit
limit, the UPS changes running mode.
Eco-mode frequency
When the frequency in the bypass is below
low limit
this limit, the UPS changes running mode.
Eco-mode frequency
When the frequency in the bypass is above
high limit
this limit, the UPS changes running mode.
External Battery
Define the number of external battery
modules***
modules.
Used to reset the UPS running time for tests
Set running time
purposes.
LCD contrast
Change the contrast in the LCD display
Battery remaining
When enabled, the battery remaining time is
time
displayed in the menu measurements
**Read Section 5.2, before using ECO-mode or converter function.
***Ensure the real battery quantity is same as indicated in the settings not to damage the batteries.
Example: Setting the rated output voltage value ( Figure 26 ).
Table 6: Settings menu information
Figure 26: Setting rated output voltage value
4NWP100559R0001_OPM_ABB_PVA31-11-T_10-20kVA_EN_140626
Modifications reserved
176~215V
245~276V
40~49.5 Hz
50.5~70 Hz
1%~10%
1%~10%
1%~10%
1%~10%
0 - 97
Day:hour:minute:second
0000:0000:00~9999:23:59:59
-5~+5
enabled/disabled
184V
264V
45 Hz
55 Hz
5%
5%
5%
5%
0
Running
time
0
enabled
Page 31/37 ABB