4.2.2.2 Procedure
1. Open the terminal block cover located on the
rear panel of the UPS.
3. Connect the wires according to the illustrations in the subsections that follow according to your
configuration (11 or 31, single or dual input feed). Pass the cables through the holes from the bottom
to the top installing also the cable glands provided with the UPS.
Note: The terminal of the phase cable must have a ring connector in some configurations.
Note: If the UPS is used as a standalone UPS, jumpers 1 and 2 must be connected. If the UPSs are used
in parallel configuration, the jumper between JP1 and JP2 must be removed.
4. Check that all wires have been properly connected.
5. Close the terminal box with the protective
cover. This is very important to prevent access
to energized cables and metal forks.
11 configuration – Single input feed
11 configuration – Dual input feed
11 configuration – Single input feed
4NWP100559R0001_OPM_ABB_PVA31-11-T_10-20kVA_EN_140626
Modifications reserved
2. Remove the protective plates of the cable
entries. (The bypass hole should remain closed
for safety purposes if it is not used)
Phase cable
Phase cable
L3 phase cable
6. Install the output breakers between the output
terminal and the load. The breaker should have
a leakage current protective function according
to the UPS voltage and current ratings.
Page 14/37 ABB