User Interactions Log; Performance Logs - Honeywell THX9321 Prestige 2.0 Product Data

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

User Interactions Log

The User Interactions Log can help a service technician save
time by determining if the issue is related to a system problem
or an accidental user error.
The User Interactions Log records the date and time for most
changes made by the user, whether made at the thermostat or
from a remote location (RedLINK Internet Gateway, Portable
Comfort Control, etc.). The log saves the most recent 250 user
changes, including:
• Indoor Air Quality Settings
• Maintenance Reminders
• Temperature Settings
• System/Fan Mode
• Alerts (snoozed or dismissed)
• Installer Setup
• Date/Time

Performance Logs

NOTE: Only applies to THX9421 Thermostat with an
Equipment Interface Module.
The Performance Log allows the service technician to quickly
check system performance over time to determine if the
equipment is operating as expected or if it requires servicing.
The thermostat contains the following logs:
• Cooling Performance Log
• Heating Performance Log
• Emergency Heat Performance Log
• Run Time by Equipment Type
• Indoor and Outdoor Conditions Log
Fig. 171.
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
The Performance Log records the following information:
• Minimum and Maximum Delta T
• Minimum and Maximum Discharge Temperature
• Minimum and Maximum Return Temperature
• Minimum and Maximum Outdoor Temperature and Humidity
• Minimum and Maximum Indoor Temperature and Humidity
• Run Time of Heating and Cooling per stage
You have the option to view this data in 4 different time periods:
• Hourly - saves data for the last 8 days.
• Daily - saves data for the last 15 days.
• Weekly - saves data for the last 8 weeks.
• Monthly - saves data for the last 25 months.
NOTES:
Data is collected in the Emergency Heat Perfor-
mance Log only if the thermostat was set to the
"Emergency Heat" mode.
The Run Time by Equipment Type Log contains
the Total Run Time of each equipment type since
the last time it was reset.
The Minimum and Maximum Delta T, Discharge
Temperature and Return Temperature are only
shown in the log if the equipment ran for at least 5
minutes during a cycle. If the equipment ran for
less than 5 minutes in every cycle during a 1 hour
period, the log will display "--°."
For Air to Air Heat Pumps, the Minimum Delta T
and Minimum Discharge Temperatures will include
defrost cycles in the log.
93
®
IAQ WITH EIM
Fig. 172.
68-0311—02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Thx9421 prestige iaq with eim

Table of Contents