Honeywell THX9321 Prestige 2.0 Product Data page 51

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
6040
Remote Setback -
Standby Heat
Setpoint
6050
What Terminals are
Wired to the Full
Drain Pan Alert Dry
Contact?
6060
Full Drain Pan Alert
Dry Contact Setup
6070
What Terminals are
Wired to the Dirty
Filter Alert Dry
Contact?
6080
Dirty Filter Alert
Dry Contact Setup
6090
What Terminals are
Wired to the Water
Leak Alert Dry
Contact?
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
50° F to 70° F
None
S1
S2
S3
S4
Normally Open
Normally Closed
None
S1
S2
S3
S4
Normally Open
Normally Closed
None
S1
S2
S3
S4
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
Residential,
Commercial
Default
or Both
64° F
Commercial
None
Both
Normally Open Both
None
Both
Normally Open Both
None
Both
51
Requires
EIM
Notes
Yes
Remote Setback requires an EIM
(Equipment Interface Module).
During occupied periods, the occupancy
sensor tells the thermostat to go to
STANDBY (setback settings) when no one
is in the room. If someone is in the room,
then it follows the settings of the occupied
period. The occupancy sensor is ignored
during unoccupied periods.
If the thermostat is setup for non-
programmable, the occupancy sensor tells
the thermostat to go to STANDBY settings
when no one is in the room. If someone is
in the room, then it follows the settings set
by the user.
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Choose an option appropriate for the type
of device installed.
Normally Open: The Dry Contact device is
normally open and will close when the
device detects the drain pan is full.
Normally Closed: The Dry Contact device is
normally closed and will open when the
device detects the drain pan is full.
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Choose an option appropriate for the type
of device installed:
Normally Open: The Dry Contact device is
normally open and will close when the
device detects a dirty filter.
Normally Closed: The Dry Contact device is
normally closed and will open when the
device detects a dirty filter.
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
®
IAQ WITH EIM