THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
10130
Ventilation High
Temperature
Lockout
10130
Ventilation High
Dew Point Lockout
10140
Lockout Ventilation
on Humidification
or
Dehumidification
Calls
10160
Ventilate on High
Indoor Humidity
10170
Ventilator Core
Cleaning Reminder
10170
Ventilator Filter
Cleaning Reminder
11000
Number of UV
Devices
11050
UV Bulb 1
Replacement
Reminder
Note: "1" is not
displayed if there is
only 1 UV Bulb
68-0311—02
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Off
80° F to 110° F (in 5° F
increments)
Off
65° F to 85° F (in 5° F increments)
Off
On
Off
On (Heat Mode Only)
Off
3, 6, 9, 12 Calendar Months
Off
3, 6, 9, 12 Calendar Months
0, 1, 2
Off, 6, 12, 24 Calendar Months
®
IAQ WITH EIM
Residential,
Commercial
Default
or Both
Off
Both
Off
Both
Off
Both
On (Heat Mode
Both
Only)
Off
Both
Off
Both
0
Both
Off
Both
62
Requires
EIM
Notes
No
Requires an outdoor sensor.
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or
Fresh Air Damper.
See "Ventilation — Outdoor Condition
Lockouts (ISU 10130)" beginning on
page 113.
No
Requires a Wireless Outdoor Sensor
(sense outdoor humidity).
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or
Fresh Air Damper.
See "Ventilation — Outdoor Condition
Lockouts (ISU 10130)" beginning on
page 113.
No
This feature is used to help reach the user's
desired humidity level by not allowing the
ventilation equipment to run during a call
for humidification or dehumidification.
Off: Ventilation is allowed to run during a
call for humidification or dehumidification.
On: Ventilation is NOT allowed to run
during a call for humidification or
dehumidification.
No
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV.
Off: The humidity level has no effect on
ventilation.
On: The thermostat removes excess
humidity by turning on the ventilator when
the indoor humidity rises 10% above the
user's humidification setting. The
thermostat must be in the heat mode to
ventilate on high humidity.
No
No
No
Press the up/down arrows to select the
number of UV devices installed in the
system. Some systems may have two UV
devices, one for the A-Coil and another for
Air Treatment. A replacement reminder can
be setup for each one. Select 0 if no UV
devices are installed.
No