Honeywell THX9321 Prestige 2.0 Product Data page 32

Hide thumbs Also See for THX9321 Prestige 2.0:
Table of Contents

Advertisement

®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
ISU
Installer Setup
Number
Name
3030
Staging Control -
Cool Differential
Stage 4
3040
Staging Control -
Radiant Heat
Differential Stage 2
3050
Staging Control -
Heat Differential
Stage 2
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type
68-0311—02
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
®
IAQ WITH EIM
Residential,
Commercial
Default
or Both
Comfort
Commercial
Comfort
Both
Comfort
Both
32
Requires
EIM
Notes
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed when the
thermostat is set to 4 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling.
For example, if stage 4 is set to 2° F (1.0°
C), the indoor temperature must be 2° F
(1.0° C) away from the setpoint before
stage 4 turns on. When set to Comfort, the
thermostat uses the stage of cooling as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed if ISU 2010
Heating Equipment Type is Geothermal
Radiant Heat and there are 2 radiant heat
stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 2 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
No
ISU 3010 Temperature Control Options
must be set to Advanced to view or adjust
this ISU.
This ISU is only displayed for conventional
systems that have 2 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 2 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to Comfort, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.