User non-configurable network inputs

Name
ni_NetSchCurrentState
ni_BypassState
ni_BypassValue
ni_DemandLimitContro
lEn
ni_OccupancySensorSt
ate
ni_VOC_Level
ni_OutsideTemp
ni_OutsideHum
ni_ShutdownState
ni_SmokeMonitorstate
ni_SpaceCO2
ni_SpaceRH
ni_SpaceTemp
52
Table 26:
User non-configurable network inputs
Default
Range
Value
1=Occupied
5=No
2=Unoccupied
Override
3=Bypass
4=Standby
5=No Override
0=Disable
Disable (0)
1=Enable
>=0
0
0=Normal
Normal (0)
1=DLCEnable
1=Occupied
5=No
2=Unoccupied
Override
3=Bypass
4=Standby
5=No Override
0-100 ppm
NA
-40-150 Deg F
NA
0-100%RH
NA
0=Normal
Normal (0)
1=Shutdown
0=Normal
Normal (0)
1=Smoke
0-2000 PPM
NA
0-100%RH
NA
-40-200 Deg F
NA
BACnet
BACnet
Object
Point
Instance
Type
ID
BACnet
1
ENUM
Value
BACnet
1
Boolean
Value
BACnet
2
Numeric
Value
BACnet
2
Boolean
Value
BACnet
6
ENUM
Value
BACnet
90
Numeric
Value
BACnet
89
Numeric
Value
BACnet
194
Numeric
Value
BACnet
4
Boolean
Value
BACnet
5
Boolean
Value
BACnet
81
Numeric
Value
BACnet
80
Numeric
Value
BACnet
104
Numeric
Value
User non-configurable network inputs
Description
Current Schedule State from
Network.
Net Bypass Input to enable
Bypass Timer
Bypass Value to enable
Bypass Time
Demand Limit Control (DLC)
input to limit the htg/ clg
demand.
Network Occupancy Sensor
State
Network Input of Volatile
Organic Compound Level.
Network Outside Humidity
Value.
Network Outside
Temperature Value.
System Shutdown input from
Network.
Smoke Detector Network
Input
Network Space CO2 Value.
Network Space RH Value.
Network Space Temperature
Value.