ISU
Installer Setup
Number
Name
4050
Outdoor
Temperature used
with Minimum Heat
Recovery Ramp
Rate
4060
Maximum Heat
Recovery Ramp
Rate
Table 4. Installer Setup (ISU) Table. (Continued)
Settings
Off
-20° F to 100°F
Off
1° F/hr to 20° F/hr
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
Residential,
Commercial
Default
or Both
0° F
Commercial
8° F/hr
Commercial
43
Requires
EIM
Notes
No
Off: The heating system will begin recovery
at the time that is scheduled.
When a Minimum Recovery Ramp Rate is
set, the thermostat will begin recovery
early to ensure the temperature is reached
at the scheduled time.
Set a Minimum Recovery Ramp Rate
based on the rate that the heating system
can recover at for a cold day in your region.
Default setting is 5° F / hour.
If an outdoor sensor is installed, set an
Outdoor Temperature that is representative
of a cold day in your region to be
associated with the Minimum Recovery
Ramp Rate. The thermostat will begin
recovery at the optimal time based on a
calculated ramp rate, allowing the system
to recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature. If there is no outdoor
sensor, the Minimum Recovery Ramp
Rate is used.
No
Off: The heating system will begin recovery
at the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery
early to ensure the temperature is reached
at the scheduled time.
Set a Maximum Recovery Ramp Rate
based on the rate that the heating system
can recover at for a mild day in your region.
Default setting is 8° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region
to be associated with the Maximum
Recovery Ramp Rate. The thermostat will
begin recovery at the optimal time based
on a calculated ramp rate, allowing the
system to recover on time and save energy
during changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
®
IAQ WITH EIM