Error code
(W#16#...)
FC 45
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
80A0
Negative acknowledgment while reading from module. FC fetches acknowledgment
although no acknowledgment is ready.
A user who is not using the FC 45 would like to fetch DS 101 (or DS 102 to104)
although no acknowledgment is available.
Perform an init_run for new synchronization between ASM and application.
80A1
Negative acknowledgment while writing to the module. FC sends command although
ASM is unable to receive a command.
80A2
DP protocol error in layer 2. Could be a hardware defect.
80A3
DP protocol error in Direct-Data-Link-Mapper or User-Interface/User. Could be a
hardware defect.
SFC not possible for module type
80B0
Data record unknown to module
Data record number ≥ 241 is not allowed.
Data records 0 and 1 are not permitted for SFC58 "WR_REC."
80B1
The length specified in the RECORD parameter is wrong.
80B2
The configured slot is not occupied.
80B3
Actual module type is not the module type specified in SDB1.
RDREC:
80C0
The module has record, but it doesn't have any read data.
WRREC:
ASM is not ready to receive new data
Wait until the cyclic counter has been incremented
80C1
The data of the preceding write job on the module for the same data record have not
yet been processed by the module.
80C2
The module is currently processing the maximum possible number of jobs for a CPU.
80C3
Required resources (memory, etc.) are currently in use.
This error is not reported by FC 45. If this error occurs, FC 45 waits until the system
is able to provide resources again.
80C4
Communication error
Parity error
SW ready not set
Error in block length management
Checksum error on CPU side
Checksum error on module side
80C5
Distributed I/O not available
Error messages and troubleshooting
Description
5.2 Error messages
5-11