Siemens SIMATIC FC 45 Function Manual page 56

Sensors
Table of Contents

Advertisement

Error messages and troubleshooting
5.2 Error messages
Error code
5-6
Flashing of
ERR LED
(B#16#..)
10
16x
11
12
18x
13
19x
14
20x
15
21x
16
22x
17
23x
18
Next command not possible or not permitted
ASM is running without MDS control (MDS_control = 0,1).
ASM has already received a Next command.
ASM / write/read device doesn't recognize NEXT command.
Short circuit or overload of the 24 V outputs (DQ, error code, presence)
The affected output is turned off.
All outputs are turned off when total overload occurs.
A reset can only be performed by turning the 24 V voltage off and
on again.
Then start init_run.
Internal ASM communication error
Connector contact problem on the ASM
Defective ASM hardware
Return ASM for repair
Start init_run command after error correction.
ASM / write/read device U does not have enough buffer to store the
command intermediately.
Internal ASM / write/read device error
Program sequence error on the ASM
Turn power of ASM off and on again.
Start init_run command after error correction.
MOBY U: Watchdog errror on write/read device.
Wrong parameterization of the ASM/SLG
Check INPUT parameters in UDT 10
Check parameters in HW Config
RESET command is parameterized incorrectly.
After a start-up, the ASM has still not received an init_run.
The FC command cannot be executed with the ASM parameters on
PROFIBUS.
Length of the input/output areas too small for the cyclic I/O word.
Did you use the right GSD file?
FC command (e.g., read) with too much user data (data length >
233 bytes).
Communication error between FC 45 and MOBY-ASM.
Handshake error
Params_DB (UDT 10) of this ASM station is being overwritten by
other parts of the program
Check parameters of MOBY-ASM in UDT 10
Check FC 45 command which caused this error
Start init_run command after error correction.
An error has occurred which must be acknowledged with an init_run.
A temporary short circuit has occurred on PROFIBUS.
The RESET command is faulty.
Start init_run command after error correction.
Check parameters ASM_address, ASM_channel, and
MOBY_mode.
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
Description
FC 45

Advertisement

Table of Contents
loading

Table of Contents