Error code
FC 45
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
Flashing of
ERR LED
(B#16#..)
19
25x
1A
1B
27x
1C
28x
1D
1E
30x
Previous command is active or buffer overflow.
The user sent a new command to the ASM although the last command
was still active.
Active command can only be terminated with an init_run.
Before a new command can be started the READY bit must be 1
(exception: init_run).
Two FC 45 calls were parameterized with the same
"ASM_address" and "ASM_channel" parameters
Two FC 45 calls are using the same Params_DB pointer.
Start init_run command after error correction.
When command repetition (e.g., fixed code MDS) is used, no data
are fetched from the MDS. The data buffer on the ASM has
overflowed. MDS data have been lost.
PROFIBUS DP error occurred.
The PROFIBUS DP bus connection was interrupted
Wire break on the bus
Bus connector on ASM was removed briefly
PROFIBUS DP master no longer addresses the ASM
Execute an init_run
The ASM has detected a message frame interruption on the bus.
The PROFIBUS may have been reconfigured (e.g. with HW
Config).
This error is only indicated when access monitoring has been enabled
in the PROFIBUS configuration.
Only with MOBY F:
CRC check in data telegram is incorrect. Checksum error between
ASM and write/read device
Interface on ASM or write/read device is defective (hardware
defect).
Check wiring of ASM-write/read device cable.
The antenna of the write/read device is turned off. An MDS command
to the ASM was started in this state.
Turn on the antenna with the command "antenna on/off."
The antenna is turned on (off) and has received an additional turn-
on (turn-off) command.
MOBY F: An FFT command was started when antenna was off
(antenna on/off with sub_command = 09).
More MDSes are in the transmission window than the SLG is capable
of processing simultaneously.
Only 1 MDS can be processed at a time with FC 45.
Error when processing the function
The data in UDT 10 are invalid (e.g. write command with length =
0); check UDT 10 and execute init_run
ASM hardware defect: ASM receives wrong data during init_run.
The "number of bytes" byte does not match the user data length
(see Section "Programming the MOBY-ASM on PROFIBUS DP-
V1").
Error messages and troubleshooting
5.2 Error messages