Requirements
● Prepare the IE POF cables with the connectors IE SCRJ POF Plug or IE SC RJ PCF
Plug.
You will find more Instructions in the installation instructions:
– POF fiber-optic cables with IE SCRJ POF plugs (A5E00351141).
– PCF fiber-optic cables with IE SCRJ PCF plugs (A5E00835119).
● When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
– IE POF/PCF standard cable: 150 mm
– IE POF/PCF trailing cable: 60 mm
● The maximum lengths of the fiber-optic cables are as follows:
– IE POF standard cable: 50 m
– IE POF trailing cable: 50 m
– IE POF standard cable: 100 m
– IE PCF trailing cable: 100 m
– IE PCF trailing cable, GI: 250 m
● When the PROFINET device is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the
BusAdapter.