Siemens SIMATIC ET 200SP Manual page 23

Busadapter
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

BusAdapter BA 2xFC
5.2 Connecting
Pin assignment
The following table shows the signal name and description of the pin assignment of
BusAdapter BA 2×FC:.
Table 5- 1
Procedure
Watch the video sequence "Connecting the BusAdapter BA 2xFC to the interface module"
(https://support.industry.siemens.com/cs/ww/de/view/95886218)
To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xFC, follow
these steps:
1. Strip insulation from the sheath of the PROFINET connecting cable as follows:
Figure 5-2
2. Pull back the locking slide and fold up the cover of the connection element.
3. Pull up the wire guide as far as it will go.
4. Insert the unstripped single cores of the PROFINET connecting cable into the cable
routing as far as it will go. Firmly press down the wire guide as far as it will go. Please
refer to the color coding.
22
PROFINET IO pin assignment with BusAdapter BA 2×FC
View
1
2
3
4
PROFINET connecting cable
Signal name
RD_N
Receive Data -
TD_N
Transmit Data -
RD
Receive Data +
TD
Transmit Data +
Description
BusAdapter
Manual, 03/2018, A5E41449003-AA