Removing/Replacing The Sram Battery - Emerson FB2100 Instruction Manual

Flow computer
Hide thumbs Also See for FB2100:
Table of Contents

Advertisement

5.6

Removing/Replacing the SRAM Battery

A lithium coin cell battery provides backup power for the SRAM and the real time clock. The SRAM
backup battery can last for up to 10,000 hours of cumulative operation, and only runs if the main
power system fails. You do not need to power down the unit to replace the SRAM backup battery.
Important
If the unit is ever powered down without the SRAM battery installed, SRAM data is lost. Always back
up your data before you remove the SRAM battery if you know that main power will also be off.
Important
Replacement SRAM backup batteries must be Rayovac® Model BR2335.
DANGER
Ensure the flow computer is in a non-hazardous area. Never open the enclousre in a hazardous
area.
DANGER
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area
is known to be non-hazardous.
DANGER
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division
2.
DANGER
EXPLOSION HAZARD: Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Batteries must only be changed in an area known to be non-
hazardous.
1.
2.
Service and Troubleshooting
Open the enclosure.
Loosen the two captive fastening screws on the cover of the black CPU enclosure (which has
the HMI module attached to it) and place it aside.
Emerson FB2100 Flow Computer Instruction Manual
D301783X012
March 2019
95

Advertisement

Table of Contents
loading

Table of Contents