Pulse Inputs; Pi Wiring; Table 3-5. Pulse Input Characteristics - Emerson FB2100 Instruction Manual

Flow computer
Hide thumbs Also See for FB2100:
Table of Contents

Advertisement

3.5

Pulse Inputs

The FB2100 flow computer with CPU option 2 includes two channels that can be individually
configured as either pulse inputs (PI), digital inputs (DI), or digital outputs (DO).
When configured as pulse inputs, the PI channels have the following characteristics:

Table 3-5. Pulse Input Characteristics

Type
Pulse
Input (PI)
3.5.1

PI Wiring

The diagram below shows how to wire the pulse inputs.
Figure 3-7. Pulse Input (PI) Wiring [DI/DO/PI1 & DI/DO/PI2]- (CPU Option 2)
1
I/O Configuration and Wiring
Number Supported
0 to 2 as follows (CPU option 2 only):
▪ 1 or 2 non-isolated channels on CPU
board (PI/DI/DO1 and PI/DI/DO2). Two
always present; you can configure one,
both, or neither as PIs.
Open Drain Type or Open Collector Device (Externally Powered)
Emerson FB2100 Flow Computer Instruction Manual
Characteristics
▪ Supports dry contacts and open
collector outputs connected to ground
and voltage inputs
▪ Supports single pulse for volume or
mass
▪ Input filtering selectable at 30 µs or 1
ms
▪ Frequency range from 0 to10.5 KHz
▪ Maximum input frequency for the 1 ms
filter is 300 Hz
▪ When a channel is configured as a PI it
cannot be used as a DI or DO channel
ON when greater than 3.0V; OFF when
less than 2.0V
D301783X012
March 2019
67

Advertisement

Table of Contents
loading

Table of Contents