Operation Range - Mitsubishi Electric GUG-01SL-E Technical Manual

Direct expansion coil unit for lossnay, lossnay return air and supply air temperature control
Hide thumbs Also See for GUG-01SL-E:
Table of Contents

Advertisement

3
Specifications
CHAPTER

1. Operation range

Outdoor air
Return air *2
+40 ˚C, 80 %RH or less
Ambient the unit
0 ˚C to +40 ˚C, 80 %RH or less
*1: -15 ˚C to -10 ˚C : Intermittent operation takes 60 min. for ON and 10 min. for OFF.
-15 ˚C or lower : Intermittent operation takes 55 min. for OFF and 5 min. for ON.
*2: Air conditioned room air.
Guaranteed operation
ranges [Outdoor]
Cooling *3
Heating
*3: The optional air protection guide is required where the ambient temperature is lower than -5 ˚C.
2. Connectable Lossnay unit and outdoor unit for each functions
Note
:
Dx-coil unit is only connectable to the Lossnay unit manufactured later than June 2016. Serial number of Lossnay unit
should be 16060001 or later.
The software version written in Lossnay PCB should be 05 or later.
[RA (Return Air) temperature control]
Dx-coil unit
Connectable Lossnay
LGH-50RVX-E
Connectable outdoor unit
PUHZ-ZRP35
[SA (Supply Air) temperature control]
Dx-coil unit
Connectable Lossnay
LGH-80RVX-E
Connectable outdoor unit
PUHZ-ZRP50
Note:
GUG-01SL-E cannot be used for the SA temperature control function.
3. Refrigerant pipe size information
Dx-coil unit
Ref. pipe size of unit
Outdoor unit
Ref. pipe size of unit
Pipe size between Dx-coil
unit and outdoor unit
*1: To change the pipe size, PAC-SH30RJ and PAC-SH50RJ are needed to be installed at Dx-coil unit side.
Dx-coil unit
A
E
B
F
Lossnay
-15 ˚C to +40 ˚C *1
Outdoor unit
PUHZ-ZRP35 and 50
-15 ˚C to +46 ˚C
-11 ˚C to +21 ˚C
GUG-01SL-E
LGH-65RVX-E
LGH-80RVX-E LGH-100RVX-E
PUHZ-ZRP35
PUHZ-ZRP50
GUG-02SL-E
LGH-150RVX-E
LGH-100RVX-E
LGH-150RVXT-E
PUHZ-ZRP50
PUHZ-ZRP71
-
GUG-01SL-E
A / B
6.35 / 12.7
-
PUHZ-ZRP35
PUHZ-ZRP50
C / D
6.35 / 12.7
6.35 / 12.7
E / F
6.35 / 12.7
6.35 / 12.7 *1
Outdoor unit
C
D
Dx-coil unit
-
-
0 ˚C to +40 ˚C, 80 %RH or less
PUHZ-ZRP71, 100 and 125
-15 ˚C to +46 ˚C
-20 ˚C to +21 ˚C
GUG-02SL-E
LGH-150RVX-E
LGH-150RVXT-E
PUHZ-ZRP71
PUHZ-ZRP100
GUG-03SL-E
LGH-200RVX-E
LGH-250RVXT-E
LGH-200RVXT-E
PUHZ-ZRP71
PUHZ-ZRP71
GUG-02SL-E
9.52 / 15.88
PUHZ-ZRP71
9.52 / 15.88
9.52 / 15.88
PZ-01RC
-
-
0 ˚C to +40 ˚C
GUG-03SL-E
LGH-200RVX-E
LGH-250RVXT-E
LGH-200RVXT-E
PUHZ-ZRP100
PUHZ-ZRP125
GUG-03SL-E
9.52 / 15.88
PUHZ-ZRP71, 100, 125
9.52 / 15.88
9.52 / 15.88
10