Mitsubishi Electric GUG-01SL-E Technical Manual page 11

Direct expansion coil unit for lossnay, lossnay return air and supply air temperature control
Hide thumbs Also See for GUG-01SL-E:
Table of Contents

Advertisement

<CAUTION>
When interlocking with Mr.Slim or external device through TM2
"OFF interlock mode" and "External priority ON/OFF interlock mode" of Lossnay unit.
DIP-SW
SW No.
Setting
5-7 OFF
5-8 OFF
(Factory setting)
SW5-7
5-7 ON
SW5-8
5-8 OFF
5-7 OFF
5-8 ON
5-7 ON
5-8 ON
Prohibition for M-NET system.
Following diagrams are bad examples. Do not construct systems same as below.
M-NET system
controller
Indoor unit
MA remote controller
(If necessary)
Group 1
Multiple systems of Lossnay
unit and Dx-coil unit in one
group is prohibited.
Lossnay and Dx-coil system
and normal Lossnay unit(s)
cannot be set in same group.
CHAPTER
PZ-61DR-E
Function No.
-
15
Lossnay unit
Lossnay remote controller
(PZ-61DR-E, if necessary)
Lossnay unit
Lossnay remote controller
(PZ-61DR-E, if necessary)
Lossnay unit
Lossnay remote controller
PZ-61DR-E, if necessary)
Group 2
2
System configurations /
and
, there is a restriction to use "ON interlock mode" ,
Interlock setting
Setting Data
0
DIP-SW priority
(Factory setting)
1
a) ON/OFF interlock mode
2
b) ON interlock mode
3
c) OFF interlock mode
d) External priority ON/
4
OFF interlock mode
Dx-coil unit
PZ-01RC
Dx-coil unit
PZ-01RC
2
.Technical notes
Available only when
PZ-61DR-E is connected
or M-NET system
controller is connected.
Not available at anytime
with Dx-coil unit.
To use M-NET adapter for the
outdoor unit is prohibited.
Outdoor unit
M-NET
adapter
Power supply
Outdoor unit
Power supply
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gug-03sl-eGug-02sl-e