Operation

Lossnay can be connected with Lossnay remoote controllers (PZ-60DR-E,PZ-41SLB-E,PZ-52SF-E),
and other Systems (City multi,Mr.slim,Central controller(MELANS))
Following shows the use of PZ-60DR-E,Please refer to the manuals for the other systems.
For connection of a Lossnay remote controller (PZ-60DR-E)
If the Lossnay's operation is linked with the operation of an external device such as an air conditioner, the method of use will differ, so carry out
the appropriate operation in accordance with the following table. Also, please see the installation and user's manual for the Lossnay remote
controller (PZ-60DR-E).
<If not connected to an external device> (PZ-41SLB-E can not be used together with PZ-60DR-E)
Example of System
Lossnay
Power Supply
<If connected to an external device> (PZ-41SLB-E can not be used together with PZ-60DR-E)
Lossnay
External device
Power Supply
Lossnay
External device
Power Supply
■ Display and Function button (PZ-60DR-E)
Timer Menu button
(Monitor / Set button)
■ LOSSNAY ENERGY RECOVERY VENTILATE
setting
Both fresh air supply and return air pass through the energy recovery
cores. Resulting in total heat exchange. Energy recovery ventilation
makes the fresh air temperature close to the indoor temperature in
the winter and the summer season.
Models LGH-15 to 100 RX
5
Damper
Exhaust air
Return air
Fresh air
Supply air
Lossnay core
2
Remote Controller
(Optional parts)
(PZ-60DR-E)
Remote Controller
(Optional parts)
(PZ-60DR-E)
Power Supply
Operation switch for the external device
Power Supply
Operation switch for the external device
Display
Function
Fan speed
ON/OFF
selector
Adjustment
button
button
button
Models LGH-150 and 200 RX
Damper
Exhaust air
Fresh air
Exhaust air
Fresh air
Lossnay core
Operation
Run using the remote
controller.
If an external device is
connected the "On/Off"
function of this device will
also control the Lossnay
operation.
■ BY-PASS VENTILATE setting
The fresh air passes through the Lossnay cores and the return room
air is exhausted direct. Lossnay bypass ventilate is normally operated
during the spring/autumn months.
Models LGH-15 to 100 RX
Exhaust air
Fresh air
Lossnay core
■ AUTOMATIC VENTILATION setting
The automatic damper mode automatically provides the correct
ventilation for the conditions in the room. The following shows the
effect "By-pass" ventilation will have under various conditions.
1. Reduces cooling load
If the air outside is cooler than the air inside the building during the
cooling season (such as early morning or at night), "By-pass"
ventilation will draw in the cooler outside air and reduce the cooling
load on the system.
2. Night purge
"By-pass" ventilation can be used to release hot air from inside the
building that has accumulated in buildings a business district during
the hot summer season.
5
3. Office equipment room cooling
During cold season, fresh air can be drawn in and used as is to cool
rooms where the temperature has risen due to the use of office
equipment.
Return air
Supply air
Return air
In the case of "By-pass" ventilation, the supply air temperature
Supply air
slightly rises more than the outside air temperature because
of the heat effect around the ducts or the unit motors.
Function
• If 2 remote controllers are used, the last
controller to be used has priority. (Last
Command)
• If you would like to turn ON the Lossnay
alone while the external device is OFF,
operate it by the Lossnay remote control-
ler.
• The fan speed is on "High".
• The ventilation mode is "Ventilation Mode
Auto Select".
Models LGH-150 and 200 RX
5
Damper
Return air
Exhaust air
Fresh air
Supply air
Exhaust air
Fresh air
Lossnay core
5
Damper
Return air
Supply air
Return air
Supply air