III : Calculation of Lossnay energy recovery effect
(A) Lossnay model
(B) Temperature exchange efficiency for summer (at 1000m
(C) Enthalpy exchange efficiency on cooling (at 1000m
(D) Lossnay outlet air temperature
= (G) – ((G) - (I)) x (B) = 33
(E) Lossnay outlet air enthalpy
= (H) – ((H) – (J)) x (C) = 84.6 - (84.6 – 52.8) x 0.71
(F) Energy recovered by Lossnay
=((H) – (E)) x ρ x Q
Note: Please see the picture below to find (G) to (J)
Dry bulb temperature
Absolute humidity
Relative humidity
Enthalpy
Total energy recovered
Ventilation load
Ventilation load ratio
Dry bulb
temperature
Absolute
Indoor Unit
humidity
of
Relative
Air Conditioner
humidity
Enthalpy
Selection of Dx-coil unit and outdoor unit
STEP2.
Dx-coil unit should be selected by connected Lossnay model shown in the table below.
Besides, outdoor unit is naturally selected by required temperature control, RA or SA.
[RA (Return Air) temperature control]
Dx-coil unit
GUG-01SL-E
Connectable
LGH-50RVX-E
Lossnay
Connectable
PUHZ-ZRP35
outdoor unit
[SA (Supply Air) temperature control]
Dx-coil unit
GUG-02SL-E
Connectable
LGH-80RVX-E
Lossnay
Connectable
PUHZ-ZRP50
outdoor unit
Note:
GUG-01SL-E cannot be used for the SA temperature control function. Refer to page 10 for pipe size information.
LGH-100RVX-E
Temperature control feature
Return air temperature control
39
- (33
- 26
) x 0.72
˚C
˚C
˚C
/3600 = (84.6 – 62.1) x 1.2 x 1000/3600
f
Lossnay outlet air
[˚C]
[
]
g/kg(DA)
[
]
%
[
]
kJ/kg(DA)
[
]
kW
[
]
kW
[
]
%
Return air
(l)
26°C
10.5 g/kg(DA)
50%
(J)
52.8 kJ/kg(DA)
LGH-65RVX-E
LGH-80RVX-E
PUHZ-ZRP35
PUHZ-ZRP50
LGH-150RVX-E
LGH-100RVX-E
LGH-150RVXT-E
PUHZ-ZRP50
PUHZ-ZRP71
Lossnay model
LGH-100RVX-E
/h)
3
72%
/h)
3
71%
28˚C
62.0kJ/kg(DA)
7.5 kW
Lossnay Unit
28
13.3
56
62.0
7.5
3.1
29
GUG-02SL-E
LGH-150RVX-E
LGH-100RVX-E
LGH-150RVXT-E
PUHZ-ZRP71
PUHZ-ZRP100
GUG-03SL-E
LGH-200RVX-E
LGH-250RVXT-E
LGH-200RVXT-E
PUHZ-ZRP71
PUHZ-ZRP71
Adequate Dx-coil unit model
Adequate outdoor unit model
Outdoor air
Dry bulb
(G)
33°C
temperature
Absolute
humidity
Relative
humidity
(H)
Enthalpy
84.6 kJ/kg(DA)
GUG-03SL-E
LGH-200RVX-E
LGH-200RVXT-E
PUHZ-ZRP100
GUG-02SL-E
PUHZ-ZRP71
Exhaust air
20.1 g/kg(DA)
63%
LGH-250RVXT-E
PUHZ-ZRP125

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gug-03sl-eGug-02sl-e

Table of Contents