Proline Prosonic Flow 91W
Cable-specification
!
power consumption
Power supply failure
Potential equalization
Endress+Hauser
Cable gland for two connection cables (2 × Q 4 mm/0.16") per cable entry
Only use the connection cable supplied by Endress+Hauser. Different versions of the connecting cables are
available ä 21.
Prosonic Flow
• Cable material:
– Prosonic Flow 91W (DN 50 to 4000/ 2" to 160") PVC (standard) or optional PTFE
– Prosonic Flow 91W (DN 15 to 65 / ½" to 2½") TPE-V
• Cable length:
– For use in a non hazardous zone: 5 to 60 m (16.4 to 196.8 ft)
Note!
To ensure correct measuring results, route the connection cable well clear of electrical machines and switching
elements.
85 to 250 V AC: <12 VA (incl. measuring sensor)
20 to 28 V AC: <7 VA (incl. measuring sensor)
11 to 40 V DC: <5 W (incl. measuring sensor)
Lasting min. 1 power cycle
HistoROM/T-DAT save measuring system data if the power supply fails
For potential equalization, no special measures are necessary.