Pego PLUSR 200 EXPERT Use And Maintenance Manual page 24

Hide thumbs Also See for PLUSR 200 EXPERT:
Table of Contents

Advertisement

5 - Datenprogrammierung - Parameter programming
in1
INP-1 digital input setting
Einstellung Digitaleingang INP-2
in2
INP-2 digital input setting
Einstellung Digitaleingang INP-3
in3
INP-3 digital input setting
Freigabe buzzer
BEE
Buzzer enable
Mindestwert,
der
werden kann
LSE
Minimum value attributable to setpoint.
Höchstwert, der dem Setpoint zugeordnet werden
kann
HSE
Maximum value attributable to setpoint.
Freigabe Tag/Nacht (Energieeinsparung)
Während des Nachtbetriebs blinkt der Dezimalpunkt.
dnE
Night mode enable (energy saving).
During night operation the decimal point flashes.
Während
des
Dezimalpunkt
(Energieeinsparung, mit In1 oder In2 oder In3 = 8
oder -8, oder tdS/tdE)
Während des Nachtbetriebs ist das Set der
Einstellung:
nSC
Set Einstellung = Set + nSC
Correction factor for the SETPOINT during night
operation
(energy saving, with In1 or In2 or In3 = 8 or -8, or
tdS/tdE).
During night operation the control set is:
Set Control = Set + nSC
Rev. 01-19
dem
Setpoint
zugeordnet
Nachtbetriebs
blinkt
GEBRAUCHS- UND WARTUNGSHANDBUCH
USE AND MAINTENANCE MANUAL
8 = Night mode digital input (energy saving)
(N.O.)
7 = Stop defrosting remotely (N.O., active on the
rising edge)
6 = Start defrosting remotely (N.O., active on the
rising edge)
5 = Stand-by remotely (N.O.) (In order to indicate
Stand-By mode, the display shows In5
alternating with the current view)
4 = Pump-down pressure switch (N.O.)
3 = Man-in-room alarm (N.O.)
2 = Compressor protection (N.O.)
1 = Door switch (N.O.)
0 = disabled
-1 = Door switch (N.C.)
-2 = Compressor protection (N.C.)
-3 = Man-in-room alarm (N.C.)
-4 = Pump-down pressure switch (N.C.)
-5 = Stand-by remotely (N.C.) (In order to
indicate Stand-By mode, the display shows
In5 alternating with the current view)
-6 = Start defrosting remotely (N.C., active on
the falling edge)
-7 = Stop defrosting remotely (N.C., active on the
falling edge)
-8 = Night mode digital input (energy saving)
(N.C.)
Wie bei 1
Like in1
Wie bei 1
Like in1
0 = deaktiviert
1 = freigegeben
0 = disabled
1 = enabled
-45 ÷ (HSE-1) °C
-45 ÷ (HSE-1) °C
(LSE+1) ÷ 99 °C
(LSE+1) ÷ 99 °C
0 = deaktiviert
1 = freigegeben
0 = disabled
1 = enabled
der
-20,0 ÷ +20,0 °C
-20,0 ÷ +20,0 °C
PLUSR200 EXPERT
S. 24
1
2
3
1
-45°C
+99°C
0
0.0 °C

Advertisement

Table of Contents
loading

Table of Contents