Meridian 1 Small System cable installation (Option 11C and
Option 11C Mini)
553-3001-202
Standard 1.00
Install and configure ITG ISL Trunk node
1
Set the switches and jumper plugs in the NTAK02 SDI/DCH card as
shown. See Tables 29 and 30.
Table 29
NTAK02 SDI/DCH switch settings for ITG ISL Trunk DCHIP
Port 1
SW 1-1
DCH
Port 3
SW 1-3
DCH
Table 30
NTAK02 SDI/DCH jumper settings for ITG ISL Trunk DCHIP
Jumper
Port
location
Port 1
J7
J6
Port 3
J4
J3
2
Connect the NTAK19FB Quad Serial I/O SDI/DCH Cable (or
equivalent) to the I/O connector for the card slot in which the SDI/DCH
card is installed.
3
If the DCHIP card is installed in the main cabinet with the SDI/DCH
card then use NTWE04AD SDI/DCH Extension Cable (1 ft.) from the
NTCW84KA DCH (P5) connector to the NTAK19FB D-Channel port
connector for Port 1 or Port 3.
April 2000
SW 1-2
OFF
OFF
SW 1-4
OFF
OFF
Strap
Jumper
for
location
DTE
C - B
J9
C - B
J8
C - B
J2
C - B
J1
RS422
C - B
C - B
C - B
C - B