Remove existing I/O panel filter adapter

553-3001-202
Standard 1.00
Install and configure ITG ISL Trunk node
Note: The NTCW84JA filter connector is required for separate subnets
using 100BaseTX for the T-LAN connection.
The standard I/O filter adapter is shielded metal with a black plastic insert
connector. The NTCW84JA adapter uses yellow warning labels to indicate
EMC filtering modifications and which MDF connection points can support
100BaseT connection.
1
Before any of the following installation steps, remove the ITG pack, or
any other IPE pack, from the IPE shelf card slot corresponding to the
I/O Panel connector to be removed.
Note: Make sure to use the I/O panel connector which corresponds to
the left slot number of the DCHIP card.
2
First remove the NT8D81AA Backplane to I/O Panel ribbon cable
assembly which will be connected to the backplane side of the existing
block by releasing the latching pins on the filter block and pulling the
NT8D81AA cable away.
3
Next unscrew the existing filter adapter from the I/O panel. There is
one screw on the lower front of the adapter and one screw on the
upper back of the adapter. Remove the adapter.
4
Re-position the new NTCW84JA filter adapter in the now vacant I/O
panel opening. (See Figure 22 on page 160.)
5
Attach the new NTCW84JA to the I/O panel by securely fastening the
top back screw and the bottom front screw.
6
Reconnect the NT8D81AA cable and secure it in place by snapping
shut the locking latches provided on the NTCW84JA connector.