Prerequisite for commissioning (KNX PL-Link)

Load application on the
room automation
station

Manual commissioning (KNX PL-Link)

Addressing

Connection test

Reset to factory setting
8 / 16
QMX3... Wall-mounted sensors and room operator units for KNX PL-Link, KNX S-mode and KNX LTE-Mode
Siemens Building Technologies
The room automation station must be running and an application must be loaded.
The application is not loaded on the room operator unit, but the room automation
station.
Download of the application is done using the SSA-DNT (Pack & Go) or the ABT.
For this purpose (or for service), connect the ABT to the room automation station
(USB or Ethernet).
All commissioning work is done via the room automation station, using the SSA-
DNT or the ABT.
The ABT is never connected directly to a room operator unit.
When more than one QXM3.P... room operator unit is on the same trunk of the
KNX PL-Link bus, manual commissioning is done as follows:
1. Connect the SSA-DNT or the ABT to the room automation station and activate
the online commissioning function.
2. Load the web page "KNX PL-Link identification".
Activate the identification function.
The room automation station now waits for a signal from the room operator
unit.
3. On the room operator unit, simultaneously press the upper left and bottom
right button for at least 5 seconds (keys 1 and 8).
4. The "Engineering" page
5. Press "Prog. Mode" (Key 2).
The display changes from "DISA" to "EnAB".
The tool identifies the current room operator unit that is operated and assigns
it.
6. After the device is commissioned, reset the device to programming mode to
"disabled" by pressing key 2.
Note: Programming mode resets to "disabled" each time the device restarts.
1. Press "Conn. Test" (key 3) to test the KNX PL-Link connection.
The display shows the result of the connection test:
2. Press key 8 to return to the engineering page.
Press "Fact. Reset" (Key 4). The device is locked and reboots within 10 seconds.
The room automation station deletes it from its device list. During this time, it is
safe to remove the device from the network.
If the bus plug remains connected, the device acts like a newly inserted device
requiring again automated or manual configuration.
Note! This operation resets all user preference data and
configuration settings to factory default.
This operation is irreversible.
is displayed.
CM2N1602en_07