Siemens Symaro QAA2890/WI Manual

Siemens Symaro QAA2890/WI Manual

Thread room sensor
Hide thumbs Also See for Symaro QAA2890/WI:

Advertisement

Quick Links

Symaro™
Thread room sensor
QAA2890/WI, QFA2890/WI, QPA2892/WI
A6V12871702_en--_a
2022-05-10
Thread room sensor
Wireless communication KNX IoT over Thread
Battery-powered:
QAA2890/WI, QFA2890/WI: 3 x alkaline batteries type AAA, 1.5 V
QPA2892/WI: 2 x alkaline batteries type AA, 1.5 V
Temperature accuracy: ± 0.3 K@21...25 ° C, ± 0.7 K@15...21 °C/25...35 ° C,
±1 K@0...15 °C/35...50 ° C
Relative humidity accuracy: ± 2 % r.h.@30...70 % r.h.,
± 5 % r.h.@0...30 % r.h./70...100 % r.h.
CO
accuracy: ± 50 ppm / ± 2 % m.v. @0...2000 ppm
2
Range of use: -15...+50 °C / 0...100 % r.h. (non-condensing) / 0...5000 ppm
Smart Infrastructure

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Symaro QAA2890/WI

  • Page 1 Symaro™ Thread room sensor QAA2890/WI, QFA2890/WI, QPA2892/WI Thread room sensor ● Wireless communication KNX IoT over Thread ● Battery-powered: QAA2890/WI, QFA2890/WI: 3 x alkaline batteries type AAA, 1.5 V QPA2892/WI: 2 x alkaline batteries type AA, 1.5 V ● Temperature accuracy: ± 0.3 K@21…25 ° C, ± 0.7 K@15…21 °C/25…35 ° C, ±1 K@0…15 °C/35…50 °...
  • Page 2: Relative Humidity

    0...100 % DC 4.5 V (3 x Wireless 1.5 V AAA digital signal alkaline batteries) 0…50 ℃ DC 3 V (2 x Wireless QPA2892/WI S55720-S552 0...100 % 0...5000 ppm 1.5 V AA digital signal alkaline batteries) Siemens A6V12871702_en--_a Smart Infrastructure 2022-05-10...
  • Page 3: Inbox Items

    SSN NO. KNX-IoT to BACnet gateway OCT200.KNBA S55812-Y102 Thread mesh extender OCT100.R S55812-Y101 Power adapter needs to be ordered separately. All documents can be downloaded from http://siemens.com/bt/download. Product documentation Title Document ID Mounting instruction A6V12816395 Quick start guide A6V12905642 CE declarations...
  • Page 4 NOTICE Radio frequency energy Interference to radio communications ● Install and use equipment in accordance with installation guide. ● Read all regulatory compliance information. Siemens A6V12871702_en--_a Smart Infrastructure 2022-05-10...
  • Page 5 Chemical vapors at high concentration in combination with long exposure times may distort the sensor reading. NOTICE Avoid direct contact with chemicals in any form. Do not touch sensitive components with bare hands or tools as this will negatively impact measurement accuracy. Siemens A6V12871702_en--_a Smart Infrastructure 2022-05-10...
  • Page 6: Maintenance

    The batteries are almost empty if LED is red and keeps fast flashing (100 ms on / 100 ms off) for 8 s and must be replaced. For optimal performance, we recommend using high performance alkaline batteries. Siemens A6V12871702_en--_a Smart Infrastructure...
  • Page 7: Regulatory Compliance Information

    1. This device may not cause harmful interference, and 2. this device must accept any interference received, including interference that may cause undesired operation FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland Ltd. could void user authority to operate the equipment. United States representative https://new.siemens.com/us/en/products/buildingtechnologies/home.html IC Statement This device complies with Industry Canada license-exempt RSS standard(s).
  • Page 8: Warranty

    Ce transmetteur ne doit pas être placé au mê me endroit ou utilisé simultanément avec un autre transmetteur ou antenne. United Kingdom conformity assessed Contact for regulatory topics: (GB) Siemens plc, Sir William Siemens House, Princess Road, Manchester, M20 2UR Radio equipment directive...
  • Page 9 Wireless digital signal (0...10000) sensor Range of use 0...5000 ppm Measuring range 0...5000 ppm Measuring accuracy at 0...2000 ppm ± 50 ppm / ± 2 % m.v. Time constant t 5 min Output signal Wireless digital signal (0...10000) Siemens A6V12871702_en--_a Smart Infrastructure 2022-05-10...
  • Page 10 EN 301489-17 EN IEC 62311 EN 300328 For use in residential, commerce, light- Electromagnetic compatibility (Applications) industrial and industrial environments EU conformity (CE) xx * RCM conformity xx * UKCA conformity xx * xx * Siemens A6V12871702_en--_a Smart Infrastructure 2022-05-10...
  • Page 11 Sensor (complete assembly) Silicone Packaging Corrugated cardboard Weight including package QAA2890/WI Approx. 204.6 g QFA2890/WI Approx. 204.6 g QPA2892/WI Approx. 226.3 g The documents can be downloaded from http://siemens.com/bt/download. Dimensions Dimensions in mm Type QAA2890/WI, QFA2890/WI QPA2892/WI Siemens A6V12871702_en--_a Smart Infrastructure 2022-05-10...
  • Page 12 Issued by © Siemens Switzerland Ltd, 2022 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID A6V12871702_en--_a Edition 2022-05-10...