Download Print this page
Siemens QFA2000 User Manual

Siemens QFA2000 User Manual

Room sensors

Advertisement

Quick Links

Use

Type summary

Type
Temperature
reference
measuring range
QFA2000
None
QFA2020
0...50 °C
QFA2040
0...50 °C
0...50 °C / − 35...+ 3 5 °C
QFA2060
CE1N1857en
06.06.2005
Room Sensors
for relative humidity and temperature
• Operating voltage AC 24 V or DC 13.5...35 V
• Signal output DC 0...10 V for relative humidity
• Signal output DC 0...10 V or LG-Ni 1000 or T1 for temperature
• Accuracy of ± 3 % r.h. within comfort range
• Range of use −15...+50 °C / 0...95 % r. h. (non-condensing)
In ventilating and air conditioning plants to acquire
• relative humidity and
• temperature
in rooms.
The QFA20... is used as a
• control sensor and
• measuring sensor for building automation and control systems or indicating units.
Temperature
signal output
None
Passive, LG-Ni 1000
Passive, T1
Active, DC 0...10 V
Humidity
Humidity
measuring range
signal output
0...100 %
Active, DC 0...10 V
0...100 %
Active, DC 0...10 V
0...100 %
Active, DC 0...10 V
0...100 %
Active, DC 0...10 V
Siemens Building Technologies
1
857
QFA20...
Operating voltage
AC 24 V or DC 13.5...35 V
AC 24 V or DC 13.5...35 V
AC 24 V or DC 13.5...35 V
AC 24 V or DC 13.5...35 V
HVAC Products
.
.
.
.

Advertisement

loading

Summary of Contents for Siemens QFA2000

  • Page 1 AC 24 V or DC 13.5…35 V 0...50 °C / − 35...+ 3 5 °C QFA2060 Active, DC 0...10 V 0...100 % Active, DC 0...10 V AC 24 V or DC 13.5…35 V Siemens Building Technologies CE1N1857en HVAC Products 06.06.2005...
  • Page 2 The measuring circuit, the sensing elements and the setting element are located on the printed circuit board inside the casing. The baseplate carries the connecting terminals. Siemens Building Technologies Room sensors QFA20… CE1N1857en HVAC Products 06.06.2005...
  • Page 3 The end of the conduit at the sensor must be sealed to prevent false measurements due to draughts through the conduit. Installation instructions Installation instructions are printed on the packing. Siemens Building Technologies Room sensors QFA20… CE1N1857en HVAC Products 06.06.2005...
  • Page 4 Degree of protection Housing IP 30 to IEC 529 Safety class III to EN 60 730 1 × 2.5 mm oder 2 × 1.5 mm Electrical connections Screw terminals for Siemens Building Technologies Room sensors QFA20… CE1N1857en HVAC Products 06.06.2005...
  • Page 5 EN 61 000-6-3 conformity to EMC directive 89/336/EEC conformity to Australian EMC framework Radio Communication Act 1992 Radio Interference Emission Standard AS / NZS 3548 Weight Incl. packaging approx. 0.13 kg Siemens Building Technologies Room sensors QFA20… CE1N1857en HVAC Products 06.06.2005...
  • Page 6 Signal output LG-Ni 1000 oder T1 (passive, simulated) for temperature range 0…50 °C; the wires must not be interchanged Dimensions Drilling plan Dimension in mm © 2004 Siemens Switzerland Ltd Subject to change Siemens Building Technologies Room sensors QFA20… CE1N1857en HVAC Products 06.06.2005...

This manual is also suitable for:

Qfa2020Qfa2040Qfa2060