Connection; Knx / Pl-Link Plug; Rj45 Plug Of The Tool Cable; Connect The Tool - Siemens QMX3.P30 Instruction Manual

Wall-mounted sensors and room operator units
Hide thumbs Also See for QMX3.P30:
Table of Contents

Advertisement

Connection

KNX / PL-Link plug

NOTICE
Tool plug
(2.5 mm Jack)

RJ45 plug of the tool cable

Connect the tool

QMX3... Wall-mounted sensors and room operator units for KNX PL-Link, KNX S-mode and KNX LTE-Mode
Siemens Building Technologies
+
Red
KNX PL-Link (positive)
Gray
KNX PL-Link (negative)
• Wires are NOT interchangeable.
The device is protected against faulty wiring, but communications does not work
on interchanged wires.
• The KNX / KNX PL-Link bus MUST NOT be connected to the tool plug,
only the tool.
Connect the ABT to load the application in the room automation station, or for
service purposes:
Directly to the room automation station.
To the room unit using the tool cable and the OCI702 service interface (see data
sheet A6V10438951).
R1
N1
5 Spannung 16 V
1 CE+, KNX
6 N.C.
2 CE−, KNX
7 Ident'pin
3 N.C.
8 GND
4 N.C.
QMX3... room operator unit
Controller, actuator
=
Twisted pair
CM2N1602en_07
15 / 16
2017-05-22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents