Remote I/O Control According To Arbitrary Allocation - Panasonic MEWNET-F Technical Manual

Remote i/o system
Table of Contents

Advertisement

6.2.2 Remote I/O Control According to Arbitrary Allocation

Register an arbitrarily allocated remote I/O map in the CPU. Remote I/O control will be conducted
according to the registered I/O map. (The base word number is according to the setting.)
Even if there is a slave station which is not activated when the master unit is turned on, the remote I/O
map (remote I/O number allocation) will not be changed.
Any slave stations activated after the master unit is turned on will be controlled by the master unit after it
is activated.
When you select the "Confirmation mode for connection of slave station" (system register No. 35) in the
CPU, the CPU controls the input/output after all of the slave stations which have been registered in the
CPU are turned on.
Reference: For information on teh "Confirmation mode for connection of slave station", <7.3 Slave
Station Connection Confirmation Mode>
In the example above, slave station number 2 is not activated or connected.However, when it is turned
on, it will be controlled according to the remote I/O map registered in the CPU.
Note:
Once the I/O map has been registered, the contol will not be performed correctly in case of
configurations with different registrations.
-When remote I/O number registration is nto done correctly for a FP I/O terminal board, FP I/O terminal
unit or FP I/O link unit, an "I/O terminal board registration error" will occur.
-When "Confirmation mode for connection of slave station" has been selected, even if there is no slave
station registered in teh CPU, the CPU will recognize that it has not been turned on yet. And the CPU
will not start the operation until the registered station is installed and turned on.
6-6