Functions of each part
Operation monitor LEDs
Station number selector switches
Mode selector switches
RS485 interface
Power supply terminals
Expansion connector
Name
Cable length
FP1
Expansion cable
11-6
Indicates communication status and operation mode.
Set the slave station number of the MEWNET-F.Point the
arrow to the number to be used. (Set tens place and ones
place separately.)
Setting range: 01 to 32
* When setting numbers exceeding the range, the setup
error occurs (ALARM LED flashes), and communication
becomes impossible.
* The settings will be accepted when the power turns on.
Sets the terminal station and the output mode a communication error
occurs.
SW
Setting
1、2
Terminal station setting
Output condition during a
3
communication error
* The output when a communication error occurred is the output Y on the
FP2/FP2SH/FP3/FP10SH.The input X corresponds on the FP1.
* The settings of SW1 and SW2 should be the same.
* The swithces are all set to the OFF position at the factory.SW4 is not used.
* The settings will be accepted when the power turns on.
Terminal for connecting with the remote master station of
FP2/FP2SH/FP3/FP10SH.A transmission cable (2-wire cable) is connected.
Supply the power to activate the I/O link unit.The AC power supply type
(AFP1736) and the DC power supply type (AFP1732) are available.
Connector for connecting to a FP1 control unit or FP1 expansion unit.For
connecting the expansion cables (refer to the table below).
* A 7 cm long cable is attached to an I/O link unit as a standard accessory.
Product No.
7 cm
AFP15101
30 cm
AFP15103
50 cm
AFP15105
OFF
Not a terminal station
Output off
Description
Standard accessory for AFP1732 and AFP1736
ON
Terminal station
Maintains its
output condition