Figure 3-7
LBS Cable Connection (20kVA)
3.5.3
Setting Parameters Of LBS
The LBS parameters setting interface is shown in Figure 3-8.
Procedures for setting LBS parameters:
Through the 'Settings' -> 'System' -> 'LBS', you can set the LBS according to actual needs.
There are three items of LBS for selection: Disable, Slave, Master.
Figure 3-8
LBS Parameter Setting Interface
The LBS is the load synchronous system, which is used to implement the output voltage phase synchronization of the
two sets of UPS system. Two sets of UPS system can be two single UPS or two sets of UPS parallel system.
Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual