Chapter 3 Electrical Installation
Silkscreen
J3
Remote EPO input
EPO is triggered when pins 3 and 4 of J3 are shorted or pins 2 and 1 of J3 are opened.
If an external EPO facility is required, pins 1 and 2 or 3 and 4 of J3 are reserved for this function. The external EPO
facility is also connected to the normally open or normally closed remote EPO switch between these two terminals
using shielded cable. If this function is not used, pins 3 and 4 of J23 must be opened and pins 1 and 2 of J3 must be
shorted.
The UPS EPO action shuts down the rectifier, inverter and static bypass, but it does not internally disconnect the mains input
power. To disconnect all power to the UPS, open the external power switch, bypass input switch, output switch and BCB after EPO
is activated.

3.2.6 RS232 Communication Port

See Figure 3-5 for the position of RS232 port. RS232 port monitors and sets parameters through connecting with
computer.
The RS232 port provides serial data and is intended for use by authorized commissioning and service personnel in
UPS commissioning and service.

3.2.7 USB Communication Port

See Figure 3-5 for the position of USB port. This port does not open to the customers, just for UPS engineer
commission and update the corresponding software parameters.
Method: Connect one end of the USB communication cable to the USB port in the communication box, and the other
end to the USB port of the computer.
The USB port provides serial data and is intended for use by authorized commissioning and service personnel in UPS
commissioning and service.
Note: To make the communication normal, do not connect the RS232 port and USB port to the computer at the
same time.

3.2.8 Parallel And LBS Communication Ports

See Figure 3-5 for their positions.

3.2.9 RS485 Communication Port

See Figure 3-5 for its position.
J3
4
Figure 3-9 Remote EOP input port J3
Table 3-8 Description of remote EPO input port
Port
Pin No.
3.1
3.2
3.3
3.4
Liebert NXC 30kVA And 40kVA UPS User Manual
+12V
UPS inside
External ports
3
2
1
Pin name
EPO activated when opened to 3.2. Pins 3.1 and
EPO_NC
3.2 have been shorted in factory
+12V
EPO activated when opened to 3.1
+12V
EPO activated when shorted to 3.4
EPO_NO
EPO activated when shorted to 3.3
Note
Meanings