Liebert Power Supply User Manual
Liebert Power Supply User Manual

Liebert Power Supply User Manual

700-2200 va 230 v

Advertisement

P
P
OWER
ROTECTION
PowerSure™ Interactive
700-2200 VA
230 V
R
U
M
SER
ANUAL
English
IMPORTANT SAFETY INSTRUCTIONS
WARNING: Do not attempt to service this product yourself except to
replace the battery. Opening or removing the cover may expose you to
dangerous voltages, even when the AC cord is disconnected from the
electrical outlet. Refer all servicing to qualified service personnel.
1. SAVE
THESE
INSTRUCTIONS.
IMPORTANT SAFETY INSTRUCTIONS. Read all safety and operating
instructions before operating the Uninterruptible Power System (UPS).
Adhere to all warnings on the unit and in this manual. Follow all
operating and user instructions.
2. This product is designed for Commercial/Industrial use only. It is not
intended for use with life support and other designated "critical" devices.
Maximum load must not exceed that shown on the UPS rating label. If
uncertain, consult your dealer. See Limited Warranty.
3. When replacing the batteries, use the appropriate Liebert-Approved
Replacement Battery Kit. Proper disposal of batteries is required. Refer
to your local laws and regulations for disposal requirements.
4. Always turn off the UPS and unplug it before starting the battery
replacement procedure.
replacement procedure. If you feel unqualified to replace the batteries,
do not open the battery door. Refer all servicing to qualified service
personnel.
5. CAUTION: Do not open or mutilate the batteries. Released electrolyte is
harmful to skin and eyes and may be toxic.
6. The mains supply socket or means of isolation must be within 2 metres
of the equipment and accessible to the operator. The UPS is designed
for data processing equipment.
7. The UPS comes with two output power leads with moulded connectors.
Do not modify the output power leads. Consult dealer if connector does
not match the load socket. UPS must be earthed at all times while in
use.
Turn UPS off before unplugging it, or the safety earth will be
removed.
8. The PowerSure Interactive models 700 VA, 1000 VA, and 1400 VA are
not supplied with an input power lead for connection to the mains supply
socket.
Use the input mains supply power lead from your data
processing equipment to connect the UPS to the mains supply. For the
2200 VA model, use the supplied 16 ampere rated input mains supply
leads. For UK supply systems, consult a qualified electrician to connect
the lead supplied for the 2200 VA model to the mains supply. Note
caution on following page.
THIS
MANUAL
To replace batteries, refer to the battery
2
CONTAINS

Advertisement

Table of Contents
loading

Summary of Contents for Liebert Power Supply

  • Page 1 Maximum load must not exceed that shown on the UPS rating label. If uncertain, consult your dealer. See Limited Warranty. ANUAL 3. When replacing the batteries, use the appropriate Liebert-Approved English Replacement Battery Kit. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal requirements.
  • Page 2: Introduction & System Description

    VAC mains supply. Models are available for 100-127 VAC supply voltages. 13. Route power supply leads so they are not walked on or pinched. 14. Never block or insert any object into the ventilation holes or other openings. Maintain a minimum clearance of 100 mm (4 inches) all around the UPS for proper air flow and cooling.
  • Page 3: Major Components

    MAJOR COMPONENTS TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide surge protection and filter electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected. AUTOMATIC VOLTAGE REGULATOR In normal operation, the automatic voltage regulator (AVR) passes mains AC power to the connected load.
  • Page 4: Rack Mount Installation

    The wires in the mains lead are colored with the following code: Green and Yellow = Earth Blue = Neutral Brown = Live As the color of the wires in the mains lead may not correspond with the colored marking identifying the terminals in the plug, proceed as follows: The green and yellow wire must be connected to the terminal in the plug which is marked with the letter “E”...
  • Page 5: Controls And Indicators

    24 hours. After 24 hours, retest the batteries. If the batteries have been retested and the top two LEDs still do not illuminate, contact your dealer or Liebert Technical Support (LTS) for a battery replacement kit. During normal mode...
  • Page 6 MINI-TOWER POWERSURE™ INTERACTIVE Fault Indicator Load/Battery Level Indicators Alarm Silence/ Battery Test Button On/Off Button Output Receptacles DB-9 Interface Port AC Inlet Intellislot™ Communications Port Circuit Protector or Fuse 700 VA 1000 / 1400 VA RACKMOUNT POWERSURE™ INTERACTIVE Utility High/Low Indicator Utility/Battery Status Indicator...
  • Page 7 OPERATION NORMAL MODE OPERATION During normal operation, mains power provides energy to the UPS. The filters and the power conditioning circuit process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The front panel displays the percentage of load on the UPS output.
  • Page 8: Communications Interface Port

    Monitoring of the UPS via a computer system is easily made with a Liebert SiteNet® 1 shutdown kit (sold separately). Consult your local Liebert representative to determine the correct software kit for your application.
  • Page 9 Do not dispose of batteries in a fire, the batteries may explode. If you feel unqualified to replace the battery, do not open the battery door. Call Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.
  • Page 10 Do not dispose of batteries in a fire, the batteries may explode. If you feel unqualified to replace the battery, do not open the battery door. Call Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.
  • Page 11: Troubleshooting Guide

    The fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational. If a problem persists consult your dealer, or contact Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.
  • Page 12 CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the input cord from the AC input power supply and from the UPS. Remove the fuse holder by inserting a flat blade screw driver into the slot and pulling out as indicated in the figure above.
  • Page 13: Rackmount Specifications

    MINI-TOWER SPECIFICATIONS Model Number PS700MT-230 PS1000MT-230 Model Rating VA/W 700 / 450 1000 / 670 DIMENSIONS: mm (in) Unit W x D x H 140 x 365 x 178 172 x 447 x 227 (5.5 x 14.4 x 7.0) (6.8 x 17.5 x 8.9) Shipping W x D x H 265 x 492 x 300 307 x 581 x...
  • Page 14: Limited Warranty

    (4) to six (6) months when not in use. If the UPS fails to conform with the above warranty within the two year warranty period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or replacements are warranted for the remainder of the original warranty period.