Liebert S600 User Manual

Liebert S600 User Manual

Single and parallel system 10kva- 20kva
Table of Contents

Advertisement

Quick Links

Liebert S600 Single and Parallel System 10kVA- 20kVA
User Manual
Version: V1.1
Revision date: September 27, 2018
BOM: 50490209008
Vertiv Co provides customers with technical support. Users may contact the nearest Vertiv local sales office or
service center.
@2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of
Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their
respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv
Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or
for any errors or omissions. Specifications are subject to change without notice.
Vertiv Energy Pvt. Ltd., India
Address: Plot No. C-20, Road No. 19, Wagle Industrial Estate, Thane – 400 604, Maharashtra, India
Homepage: www.vertivco.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the S600 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Liebert S600

  • Page 1 Liebert S600 Single and Parallel System 10kVA- 20kVA User Manual Version: V1.1 Revision date: September 27, 2018 BOM: 50490209008 Vertiv Co provides customers with technical support. Users may contact the nearest Vertiv local sales office or service center. @2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co.
  • Page 3  Application Note: S600 UPS is suitable for IT load applications such as computers, servers, routers, CCTV, banking automation equipments, scientific equipments, projector, POS, etc. The UPS is suitable for industrial customer for above load and UPS should be installed in AC environment. The UPS is not suitable for industrial load such as...
  • Page 4 This manual contains information concerning the installation and operation of the Liebert eXM UPS single UPS module and parallel system 80kVA ~ 200kVA. Read this manual thoroughly before installing, using and servicing the UPS.
  • Page 5 Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities. General safety (For users) Like other types of large power equipment, the UPS and battery circuit breaker box/battery cabinet Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 6 When the internal fuse of the UPS is damaged, it must be replaced with fuse of the same electric parameters by qualified personnel. Important Beside the communication board is a static sensitive area, an ESD-proof action is critical before contacting with this area. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 7: Vertiv|Liebert® S600 10Kva ~ 20Kva Ups | User Manual

    Revision Information V1.0 (August 21, 2018) Initial release. V1.1 (September 27, 2018) Revision 1 V1.2 (October 11, 2018) Revision 2 Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 8: Table Of Contents

    2.6.3 Battery Mode Start-Up ............................... 24 Chapter 3 Parallel UPS Installation and Commissioning........................26 3.1 Features ....................................26 3.2 Requirements ..................................26 3.3 Connecting Power Cables............................... 27 3.3.1 Connecting Power Cables ............................27 Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 9 5.6 Auto Restart ................................... 62 5.7 Language Selection ................................62 5.8 Changing Current Date and Time ............................64 5.9 Setting Password ..................................65 Chapter 6 Communication ..................................69 6.1 Installing Intelligent Card ............................... 69 Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 10 8.1 Option List ..................................... 78 8.2 Communication Cables ................................78 Appendix 1 LCD Parameter Settings ..............................80 Appendix 2 Glossary ..................................... 82 Appendix 3 Hazardous Substances or Elements Announcement ......................83 Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 11: Chapter 1 Product Information

    Chapter 1 Product Information S600 10~ 20kVA UPS is an intelligent online UPS system with sine wave output developed by Vertiv Co. The UPS offers reliable and high-quality AC power to the precision instrument. This chapter introduces the features, model configurations, appearance and components, operating principle, UPS state and operation mode, and specifications of the UPS.
  • Page 12: Appearance And Components

    Front Panel As shown in Figure 1-2, the UPS front panel provides ventilation holes, operation and display panel , LED indicators and functional keys. Display Panel Figure 1-2 UPS front Panel Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 13 Bypass MCB Q2 Output MCB Q5 Input MCB Q1 Maintenance Bypass MCB Q3 Power Module Battery Fuse Holder Contactor KM1 Figure 1-3 UPS Rear side Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 14: Operating Principle

    4. After the mains returns to normal state, the UPS will automatically transfer from Battery mode to Normal mode, the mains supply DC power to the inverter through the rectifier/PFC circuit, and then the electronic transfer switch supplies AC power to the load. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 15: Ups State And Operation Modes

    Normal mode. However, if the bypass failure or abnormal bypass voltage appears when the output is overloaded, the UPS will not transfer to Normal mode, but shut down the bypass. 2. In ECO mode, the efficiency of the UPS is up to 94%. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 16: Fault State

    When the UPS has malfunctions, and can not working normally, please get in touch with the nearest Vertiv branch office or local service center. It is prohibited to repaire the UPS by yourself, otherwise the personnel injury and damage to the equipment will occur. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 17: Specifications

    At 25°C: 105% ~ 125%- 5min; 125% ~ 150%-1min; 150%- more Capability the utility mode than 200ms Inverter Overload Capability the battery mode At 25°C :105% ~125%-60~ 30 s; >125%- more than 200ms Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 18 Powder coated Black Texture finish Cable entry Bottom Note: (1) UPS power will derate to 70% of the total capacity (2) UPS power will derate to 80% at 40 deg and 70% at 50 deg Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 19: Chapter 2 Installation And Commissioning

    If any problem is found, please notify the carrier immediately. Check the accessories and models against the delivery list. If any problem is found, please notify the dealer immediately. Figure 2-1 Unpacking the UPS Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 20: Equipment's Accessories

    If necessary, an indoor exhaust fan should be installed to keep the indoor temperature from rising. An air filter should be used in a dusty environment where the UPS is to be operated. Space Reserved Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 21 During the battery storage, the battery must be periodically charged according to the battery instructions. When charging the battery, you can connect the UPS to the mains temporarily to charge and activate the battery. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 22: Selecting Power Cables

    Fuse/MCB capability of capability of external MCB Selection output external Maintenance bypass external 10(3-in 1-out) 32A (mains) 63 A 63A (bypass) 20(3-in 1-out) 63A (mains) 125A 125A 125A (bypass) Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 23: Connecting Battery Cables

    3. Finish and check the parameter settings of the single UPS. a) At main menu screen, press the key to select 'Settings', and press the key to enter the interface shown in Figure 2-4. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 24: Battery Mode Start-Up

    The alarm indicator will be yellow, and the buzzer will beep continuously after the rectifier finishes the startup. 2. Press the power button for two seconds, the LCD prompts a dialogue box shown in Figure 2-7. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 25 Figure 2-7 Turning on UPS After selecting 'YES', the inverter starts, and the run indicator (green) is on. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 26: Chapter 3 Parallel Ups Installation And Commissioning

    5.2 Transfer Procedures Between Operation Modes. Failure to observe this may affect the reliability of the load power supply. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 27: Connecting Power Cables

    The parallel system provides parallel cable option. The parallel cables form a ring connection through the parallel ports on the rear panel of the UPS. Taking 20kVA model for example, the cable connection schematic diagram of 3 + 1 parallel system is shown in Figure 3-1. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 28: Connecting Battery Cables

    Figure 3-2 (a) and (b). Refer to 2.4 Connecting Power Cables to configure an MCB. Make sure that the LCD settings are correct when using the battery strings independently for the parallel system, refer to 3.5.2 Parallel System Parameters Settings for details. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 29 Figure 3-2 Connection Principle Diagram upon using battery string independently in (a) 10kVA and (b) 20kVA respectively Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 30 UPS in the parallel system through each battery MCB, as shown in Figure 3-3. Figure 3-3 Connection diagram fof shared battery string in 1+1 parallel system Refer to Figure 3-4 to configure the positive battery string and negative battery string. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 31: Commissioning Of Parallel Cables

    3.4.2 Parallel System Parameters Setting The parallel parameters for all the UPSs in the parallel system should be set. As shown in Figure 3-5. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 32: Power-On Commissioning For Parallel System

    If the UPS is working normally, press the power button for two seconds to turn off the inverter. h) Repeat the preceding step a) ~ step g) to power on and commission the inverter of other UPSs respectively. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 33 The user should manually set other parameters according to actual needs. 3. When adding a single unit in the parallel system, first ensure the parallel cables connection is correct, then power on the single unit. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 34: Installation And Commissioning For A Dual Bus System (For 20Kva System Only)

    The appearance of the LBS port is the same as the parallel port. For the dual bus system formed by the parallel UPS, it is recommended to prepare two LBS cables used to connect any two parallel/LBS ports of the two-parallel system, which is used for reliable connection.LBS connection is applicable for only 20kVA. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 35: Setting Parameters Of Lbs

    The LBS is the load synchronous system, which is used to implement the output voltage phase synchronization of the two sets of UPS system. Two sets of UPS system can be two single UPS or two sets of UPS parallel system. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 36 Through the above to realize the inverter voltage phase synchronization of two sets of UPS system and realize the reliable transfer between the two sets of UPS output voltage and STS, then provide the reliable uninterrupted power supply to the load. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 37: Chapter 4 Operation And Display Panel

    UPS and query all the UPS parameters, UPS and battery states, and alarm message. As shown in Figure 4-1, the operation and display panel provide LCD, menu keys, LED indicators (run indicator and alarm indicator). Figure 4-1 LCD Screen Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 38: Led Indicator

    The operator control and display panel provides five control keys, as described in Table 4-3. Table 4-3 Description of Control Keys Control key Silkscreen Description Confirm Used to confirm or enter Used to page up, turn left or add value, etc. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 39: Initial Start-Up Guidance

    The LCD also stores historical alarm records that can be retrieved for reference and diagnosis. 4.2 Initial Start-Up Guidance When the UPS is the initial start-up, the interface shown in Figure 4-3 will appear to guide the user to set basic parameters of the UPS. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 40 For 10kVA model, the 'Battery series' are 12, 16, and 20 selectable. See left diagram in Figure 4-5. For 20kVA model, the 'Battery series' are 24, 32, and 40 selectable. See right diagram in Figure 4-5. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 41 Figure 4-7. For 20kVA model, the 'Output phase No.' can be set to 'single' or '3 phases'. See right diagram in Figure 4-7. Figure 4-7 Initial start-up guidance (4) Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 42 4-10, confirm that the actual wiring method of the output terminal is the same as that of the setting method, then power on the UPS again. After the start-up, the user can operate the UPS normally, Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 43: Lcd Menu Structure

    4.4 LCD Screen Types 4.4.1 Start Screen Upon UPS start-up, the UPS executes the system self-test, and the start screen will appear and remain for about 10 seconds, as shown in Figure 4-12. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 44: Flow Screen

    Flow Screen 4.4.3 Main Menu Screen The main menu screen is composed of six icons: Status, Settings, Control, Log, About, Maintain. As shown in Figure 4-14. Figure 4-14 Main Menu Screen Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 45: Submenu Screen

    For details about the submenu screen, see following pages. Status page The Status page contains the Input, Bypass, Battery, Output and Load. See below Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 46 Settings page The Settings page contains the Output, Battery, Parallel, Monitor, System, and Outlet. For details about the parameters setting, refer to Appendix 1 LCD Parameters Setting. See below: Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 47 Control Page The Control page contains the Turn ON/OFF/to BYPASS, and Manual battery test, etc. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 48 See below: Log page The Log page contains the Current and History. See below: About page The About page contains the Product, Network, and Efficiency. See below: Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 49: Default Screen

    During the UPS operation, if there is no alarm within two minutes, the default screen shown in Figure 4-15 will appear. At the default screen, if there is an alarm or a fault, or the user press any key, the Flow screen will appear again. Figure 4-15 Default Screen Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 50: Prompt Window

    1 phase, 3 phase, then connection, then power on the UPS again to guarantee the power UPS on safety Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 51: Ups Alarm Message List

    Detect the parallel cables are loosened Connection abnormal Input neutral lost The AC input mains N line is not detected. Please check that the input N line is opened or loosened Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 52 The system can automatically start after overtemperature fault is System overtemp solved. If overtemperature, please check: 1. Ambient temperature too high or not 2. Dust is blocked or not 3. Fan fault or not Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 53 Confirm the parallel system load capacity, if overloaded, just reduce it Loss of After the parallel redundancy is enabled, the system load capacity is larger than the rated load of (online set minus one) Redundancy Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 54 The bypass is abnormal, and the bypass is in standby state from working state. bypass abnormal Check that thebypass input is normal Battery to The UPS is powered by the mains instead of the battery Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 55 The inverter short circuit or the bypass short circiut. Please check it output short Output off due to overload & The output is off due to output overload and bypass abnormal. Please check it bypass abnormal Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 56 If the alarm is caused through setting the software value by Vertiv authorized engineer, and when you wish to change the setting values, please get in touch with the Vertiv local customer service center. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 57: Chapter 5 Ups Operation Instructions

    In standby mode, press and hold the power button. If the rectifier and inverter are normal, the interface shown in Figure 5-1 will appear, select 'YES' to turn on the UPS. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 58 In Inverter mode, press and hold the power button. If the bypass is abnormal, then the interface shown in Figure 5-3 will appear, select 'YES' to shut down the UPS output. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 59: Transfer From Bypass Mode To Inverter Mode

    Figure 5-1 ECO Mode not turned on Select 'Turn on UPS' and click OK to transfer to the Inverter mode, see Figure 5-5. Select 'Turn off UPS' and click OK to shut down the UPS output. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 60: Transfer From Inverter Mode To Maintenance Bypass

    Otherwise, it may result in the load power interruption for a while. 1. Through the LCD settings page, change the Dry connect 3 to 'Maintain mode'. See Figure 5-7 . Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 61: Transfer From Maintenance Bypass To Inverter Mode

    Just unplug the terminal connecting to the REPO if you need emergency power-off. If the mains input is present, the UPS control circuit will remain active; however, the output is closed. To remove all Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 62: Auto Restart

    'Settings', then press the key to confirm it. See Figure 5-9. Figure 5-5 Main menu 2. Press the key to move the cursor to 'Monitor', see Figure 5-10. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 63 LCD contents will be the language selected by you. See Figure 5-12. Figure 5-8 Changing Language 5. Press the key for several times to back to the main menu screen. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 64: Changing Current Date And Time

    'Monitor', see Figure 5-14. Figure 5-10 Monitor Interface 3. Press the key, and press the or key to highlight the date and time, see Figure 5-15. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 65: Setting Password

    1. After powering on the UPS, at the main menu screen, press the key to move the cursor to select 'Settings'. See Figure 5-17. Figure 5-13 Main menu 2. Press the key, the interface shown in Figure 5-18 will appear. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 66 2. Press the key, then press the key to select the 'Change settings password', see Figure 5-20. Figure 5-16 Changing setting password 3. Press the key, the interface shown in Figure 5-21 will appear. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 67 Figure 5-23. Figure 5-19 Confirming new password 6. After the confirmation, press the key and the system prompts that the password changing is successful, see Figure 5-24. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 68 Figure 5-20 Password changed ok Only through the correct password (default: 111111) verification can you conduct the parameters of the UPS. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 69: Chapter 6 Communication

    SIC card and RDU-SIC card. The intelligent card port and USB port can be used at the same time. Intelligent Card Port Figure 6-1 Intelligent card installation (20kVA, rear view) Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 70: Intelligent Card Option

    Refer to the corresponding user manual for the installation and operation guide RS485 card RS485 card should be used together with S600 Model provided by Vertiv to realize the signal transform from RS232 to RS485. Refer to the corresponding user manual for the installation and operation guide.
  • Page 71: Connection Cables For Dry Contact Port

    RS232 card The RS232 card should be used together with the Liebert® S600 series UPS of Vertiv. It only supports RS232 protocol communication, and the maximum length of the communication cable cannot exceed 15 meters. 6.2 Connection Cables for Dry Contact Port The UPS provides five dry contact ports.
  • Page 72 1. It is recommended to use 0.82mm2 ~ 0.33mm2 (signal cable of 18AWG ~ 33AWG) copper core cable. 2. If the switch you have configured is of electronic control tripping function, when the REPO signal takes action, you need to close the switch before restart the UPS. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 73: Connecting Usb

    UPS, so as to make the computer communicate the UPS well. To change the network parameters of the UPS, operate them via the 'Settings'->’Monitor’, as shown in Figure 6-4. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 74 To obtain the best user experience, it is recommended to use the Internet Explorer (IE9 or above), or the Chrome, FireFox (latest version required) Screen resolution The display with resolution of 1024*768 or above is recommended. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 75: Chapter 7 Maintenance

    Prevent small current discharge. Continuous battery operation time exceeding 24 hours is strictly prohibited • Charge the battery for at least 12 hours, if the battery hasn't been charged for three months at specified ambient temperature, or two months at high ambient temperature Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 76: Cleaning Ups

    2. Check if the UPS is operating in Bypass mode. Normally, the UPS operates in Normal mode; if it is operating in Bypass mode, you should find out the reason, such as operator intervention, overload, internal fault, and so on . Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 77: Checking Ups Function

    1. Press the power button to check if the buzzer beeps, indicators are on and the LCD display is normal. 2. Press the ESC key to check again if the indicators are on, the LCD display is normal and the UPS has been transferred to the inverter mode. Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 78: Chapter 8 Options

    324922020703 are needed in 1 + 1 parallel system; three communicatio cables needed in 2 + 1 parallel system; four communication cables are needed in 3 + 1 parallel system Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 79 The LBS cables are compulsory in dual bus system. See Table 8-7 for the dual bus parts. Type Name Description Appearance 324922020704 LBS Cable Be used to form LBS system. LBS cables are recommended Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 80: Appendix 1 Lcd Parameter Settings

    System parallel No. 1~4 Output phase No. 1 phase, 3 phases 3 phases (/20kVA) Sync parallel parameters Button Button Shared battery Disable, Enable Disable; /20kVA only Local/Parallel battery 7~3000Ah 9Ah (5/6/10kVA) Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 81 ( 'd' is a Subnet mask 255.255.255.0 decimal number) Gateway address 192.168.1.1 Change settings password The password is numeric 111111 only and can be set from 0 to 9. The password length is 6 Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 82: Appendix 2 Glossary

    Network Management System Protective Earth RCCB Residual current circuit breaker Residual current detector REPO Remote emergency power off Silicon-controlled rectifier SNMP Simple network monitoring protocol Static transfer switch Uninterruptible power system Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...
  • Page 83: Appendix 3 Hazardous Substances Or Elements Announcement

    ×: Means the content of the hazardous sustances in at least one of the average quality materilals of the parts is outsides the limits specified in GB/T 26572 Applicable scope: Liebert® S600 10kVA ~ 20kVA UPS Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual...