Configuration Setting

For the UPS system to be aware of the presence
of the Extended Battery Cabinet(s), the system
has
to
be
configured
information. To enter the information, follow the
steps below:
After initialization, pressing the
take you to the main menu.
Scroll down to UPS Configuration, and select
it by pressing the
Main Menu
UPS Status
> UPS Configuration
Display Date/Time
Event Log
Alarm Log
Transfer to Bypass
Module Replacement
Tools
Scroll down to Change Settings; press
UPS Configuration
UPS Configuration
Review Settings
> Change Settings
Service Mode
with
the
necessary
button will
button.
Scroll down to Intellislot Battery Ca.; select it
by pressing
Change Settings
Input Voltage
Frequency Sync Range
Frequency Slew Rate
Set Password
Auto Battery Test
Low Battery Warning
Auto Restart
User Settings
Set Date/Time
Max Load Alarm Set
UPS Shutdown Delay
Redund Alarm Set
Service Contact
Remote Shutdown
External Battery
Bypass Alarm Mode
> Intelli-Batt Ca.
Air Filter Reminder
Factory Defaults
Enter the quantity of Extended Battery Cabi-
nets installed.
Press
return arrow and then press
save your changes and exit.
The system is now configured.