Figure 16 Options Diagram; Lbs Mode (Load Bus Synchronization) - Liebert NX series Operation & Maintenance Manual

10-30kva 208v, 60hz
Table of Contents

Advertisement

4.2

LBS Mode (Load Bus Synchronization)

The function of LBS is to keep the output of two independent UPS systems (single unit or multiple
unit) in synchronization even when the two systems are operating in different modes (bypass/
inverter) or on batteries. It is usually used with an STS (Static Transfer Switch) connected to the crit-
ical load to achieve dual bus configuration.
CAUTION
!
In LBS configuration, both units must be supplied from the same utility source.
4.3
Battery Start (Optional)
With this option, the NX UPS can be started with power supplied only by the batteries (at charged
condition). This type of start, in the absence of utility power, allows independent utilization of battery
power and provides for higher availability in some circumstances.
CAUTION
!
Before attempting to start the UPS without utility power present, ensure that the batteries
are fully charged—over 2.1V per cell—and will supply adequate run time to the load.

Figure 16 Options diagram