Daikin RMKS112LV1A Service Manual page 17

11.2/14.0/16.0 kw class 48000 btu/h class
Table of Contents

Advertisement

Si181296_A
Step
3
Disconnect the lead
wires of the high
pressure switch.
4
Remove the screw and
remove the solenoid
valve coil for hot gas
bypass.
5
Remove the screw and
remove the solenoid
valve coil for unloading.
Removal Procedure
Procedure
Low pressure sensor (S1NPL)
High pressure switch (S1PH)
Solenoid valve coil for unloading (Y3S)
(R12977)
(R12978)
Solenoid valve coil for
hot gas bypass (Y2S)
(R12979)
(R12980)
Outdoor Unit
Points
The pressure sensor is
equipped with a gauge port
with check valve. Therefore,
when loosening the nut,
refrigerant leak stops.
15