Outdoor Unit
Step
6
Remove the 3 nuts of
the compressor.
Cut off the suction pipe,
7
discharge pipe and
unloader pipe of
compressor with a pipe
cutter (3 places).
Remove the
8
compressor.
9
Heat up and disconnect
the brazed parts and
remove the remained
pipes.
20
Procedure
Suction
pipe portion
Compressor
Discharge pipe portion
You can see the rear side
nut when the lower
discharge grille is removed.
Remove the nuts in view
first.
(R9269)
Unloader pipe
portion
(R12986)
Si181296_A