12  KNX/EIB Control Interface: Crestron CGEIB-IP
Example: When the Crestron controller changes the value of the KNX group address
0/0/1 from 0 to 1, the CGEIB-IP will return this command resulting in immediate
feedback on the button. It is advised to have this "always activated".
 Baudrate:
Choose between 9600 and 38400. It is advised to use 38400.
 Transmit limit:
Transmission limitation of telegrams: 2, 5 or none. It is advised to use 5
Important: this can influence the bus-load, for example the response speed to
Crestron. Switching of the limiter should only be done when possible, after
verification with the KNX installer.
Be aware that adjustments to checkboxes described above need to be uploaded with
the address list to confirm the adjustment.
More information on these options can be found in the KNX software.
Note
Minimal software requirements: Microsoft.NET Framework 2.0 or
higher. (Freely available from the Microsoft website)
The CGEIB-IP should be loaded with firmware 7.03. Every CGEIB-IP
can be updated with this firmware via the KNX-Gate software.
(Firmware Gateway_Flash_C7v03.H86)

Installation

 Attach the Crestron CGEIB-IP to the DIN rail.
 Connect the serial or the CAT5 cable
 Connect the KNX bus
 Connect the power source to power up the CGEIB-IP
Crestron CGEIB-IP
Operations & Installation Guide – DOC. 0009