Programming
The following parameters are not reset during the initiali-
zation:
Parameter 8-30 Protocol
Parameter 8-31 Address
Parameter 8-32 Baud Rate
Parameter 8-33 Parity / Stop Bits
Parameter 8-35 Minimum Response Delay
Parameter 8-36 Maximum Response Delay
Parameter 15-00 Operating hours to
parameter 15-05 Over Volt's
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter 15-30 Alarm Log: Error Code
7
7
Parameter group 15-4* Drive Identification
parameters
Initialization using [OK] and [Menu] keys:
1.
Power off the frequency converter.
2.
Press [OK] and [Menu].
3.
Power up the frequency converter while still
pressing the keys for 10 s.
4.
The frequency converter is now reset, except for
the following parameters:
The LCP display shows alarm 80, Drive initialised to default
value after the power cycle.
64
®
VLT
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter group 15-4* Drive identifi-
cation parameters
Danfoss A/S © 01/2016 All rights reserved.
Micro Drive FC 51
MG02K402