PM SERIES

3.4 UPS Module LCD Control Panel

(1) LED(from top to bottom: "alarm", "bypass output", "battery output", "mains output")
(2) LCD display
(3) scroll button
(4) Off button
(5) On button

3.5 Installation Notes

NOTE:
Consider for the convenience of operation and maintenance, the space in front and back of the
cabinet should be left at least 100cm and 80cm respectively when installing the cabinet.
• Please place the UPS in a clean, stable environment; avoid the vibration, dust, humidity,
flammable gas and liquid, corrosive. To avoid from high room temperature, a system of room
extractor fans is recommended to be installed. Optional air filters are available if the UPS
operates in a dusty environment.
• The environment temperature around UPS should keep in a range of 0℃~40℃. If the
environment temperature exceeds 40℃, the rated load capacity should be reduced by 12% per
5℃. The max temperature can't be higher than 50℃.
• If the UPS is dismantled under low temperature, it might be in a condensing condition. The UPS
can't be installed unless the internal and external of the equipment is fully dry. Otherwise,
there will be in danger of electric shock.
• Batteries should be mounted in an environment where the temperature is within the required
specs. Temperature is a major factor in determining battery life and capacity. In a normal
installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries
away from heat sources or main air ventilation area, etc.
WARNING!
UDD-SD-125/ Release Date: 20.01.2015/Rev No: 0/Rev.
LCD control panel introduction