USER MANUAL POWERPACK SE SERIES 6 - 20 KVA...
Page 2
POWERPACK SE SERIES 6-20 kVA CONTENTS USER MANUAL POWERPACK SE SERIES 6 - 20 KVA UDD-SD-112...
Page 3
POWERPACK SE SERIES 6-20 kVA CONTENTS About The Manual This manual is prepared for the users of Powerpack SE Series 6-20 kVA. Companion Manuals For further information about this device and its options, please visit www.makelsan.com.tr Updates Please visit www.makelsan.com.tr for updates. Always use the latest manuals.
POWERPACK SE SERIES 6-20 kVA CONTENTS CONTENTS 1 SAFETY INSTRUCTIONS .............................. 6 1.1 UPS Safety Instructions ............................6 1.2 Battery Safety Instructions ..........................6 2 FEATURES ..................................7 2.1 Unpacking Inspection ............................7 2.1 UPS Rear Panel View ............................. 8 3 INSTALLATION INSTRUCTIONS ..........................
Page 5
POWERPACK SE SERIES 6-20 kVA CONTENTS 4.6.4 Low Battery Voltage Shutdown Point Setting ................. 26 4.6.5 Frequency Converter Mode Setting ..................... 27 4.6.6 Output Frequency Setting in CUCF Mode ..................28 4.6.6 ID Setting ................................ 28 4.7 Parameters Inquiring Operation ......................29 5 WORKING MODE INTRODUCTION ........................
1 SAFETY INSTRUCTIONS 1.1 UPS Safety Instructions Before applying the UPS system, Please read through all safety information and operating instructions carefully. It’s recommended to save this manual properly for future reading. Do not install the UPS system near the water or in moist environments. ...
2 FEATURES 2.1 Unpacking Inspection Open the UPS package, please check the enclosed accessories including user manual, RS232 communication cable, USB cable and CD-ROM. Check the UPS if anything damaged in transport. If find something damaged or parts missing, do not power on, please turn to the carrier and dealer.
3 INSTALLATION INSTRUCTIONS 3.1 Attention items of Installation The UPS installation environment must be with good ventilation, away from water, flammable gases and corrosive entities. Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air outtake hole will be unobstructed.
NOTE When connecting, please make sure to connect input cables and output cables with terminals firmly. When the input is three-phase, if the UPS is working on Bypass mode, the total current goes through phase R, so the line widths of phase R must be the same as output. When the input is single-phase, before doing input connection, users have to use two short wires to connect R&S and S&T.
3.3 Parallel System of 6-20K UPS Installation Only 6-20K UPS and containing parallel ports can do parallel operation, other types is not supported. N+X parallel structure is the most reliable power supply structure at present, N stands for the minimum number of UPS for the load, X stands for the number of redundant UPS,X absolutely means how many UPS could be malfunctioning at the same time and the parallel UPS system is still steady.
Page 12
>Installation procedure: ① Install parallel wires. Two UPS to form an UPS parallel system, in order to ensure the reliability of the parallel system, there is only one way to wire two UPS, use two parallel wires to connect two UPS like the diagram showing below, connection looks like a circle. If three or more than three UPS are needed, the connection is similar, you can refer to the diagram as below.
Page 13
Parallel Parallel Card 6KVA &10KVA Parallel Card 15KVA &20KVA Parallel Card Short Pin ②Connect output cables of all UPS together to a common terminal block. ③Connect input cables of all UPS together to one common utility power terminal block. U t i l i t y p o w e r s u p p l y I n p u t c o m m o n t e r m i n a l b l o c k O u t p u t c o m m o n t e r m i n a l...
BAT+ BAT- BAT+ BAT- INPUT BAT1 BAT2 OUTPUT Wiring diagram for two UPS parallel system BAT+ BAT- BAT+ BAT- BAT+ BAT- INPUT BAT1 BAT2 BAT3 OUTPUT Wiring diagram for thee UPS parallel system ④ If the UPS is the standard type, each UPS has batteries inside already. If the UPS is the long- run type, each UPS should be equipped a individual battery pack.
>Turn off the parallel system Hold on the OFF KEY of any one UPS of system for more than 4 seconds, it would turn off the whole parallel system. Hold on the OFF KEY of any one UPS of system for more than 1 second(less than 4 seconds), it would turn off single UPS you choose, of course if you need to turn on it again or turn on any other single UPS of the system, just press ON KEY of that UPS to start it.
3.5 Network Functions 3.5.1 Communication Port Users could monitor the UPS system through the communication port such as standard RS232 port and standard USB port with computer. With a communication wire to connect UPS and computer, could simply achieve UPS management. ☆RS232 port:...
3.5.2 EPO Port EPO is short for Emergency Power Off, EPO port is on rear panel of UPS, it’s green, in some emergent cases, users could cut off the output of UPS immediately by operating EPO port. Wiring diagram as below: Normally, pin1 and pin2 are connected so that the machine can be working normally.
3.7 Bat ttery Pack Selecting There a re two optio ons of batte ery group qu uantity for u users to cho oose, 16 uni ts and 20 u nits. The default quantity is 16 units, b but this ser ries UPS ar re also allow wed to con...
4 PANEL FUNCTION and OPERATION The operation is simple, operators only need to read the manual and follow the operation instructions listed in this manual without any special training. 4.1 Keys Function ※ ON KEY ( Press and hold the two keys for more than half a second to turn on the UPS. ※...
※ FUNC CTION SETT TING KEY Non-fun nction settin ng mode: Press an nd hold the k key for mor e than 2 sec conds: Funct tion setting interface. Function n setting mo ode: Press an nd hold the k key for mor e than half a a second (le...
Page 22
※ Icon display area: A. The top diagram is for load and battery capacity indication, each grid of which represents 25%. When UPS is over load, the load light will blink the same as the battery light blink when the capacity of battery get low or battery disconnected. B.
4.4 Single UPS Turn On/Off Operation 4.4.1 Turn On Operation > Turn on the UPS on line mode 1. Once mains power is plugged in, the UPS will charge the battery, at the moment, LCD shows that the output voltage is 0, which means UPS has no output as default condition. If it is expected to have output of bypass, you can set the BPS “ON”...
4.5 Single UPS Self-Test/Mute Test Operation 1. When UPS is in LINE Mode, press and hold the self-test/mute key for more than 1 second, LED light will go off circularly and orderly. UPS comes to self-test mode and tests its status. It will exit automatically after finishing test.
4.6.2 Input Methods Setting 1. Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, press and hold the inquiring key ( ) for more than half a second(less than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the letters “IPP”...
voltages are 208V, 220V, 230V, 240V, you can choose anyone by yourself (The default value is 220V). 3. Confirm the output voltage setting interface. After selecting numerical value, press and hold the function setting for more than half a second (less than 2 seconds). Now, the OPU setting function is completed and the numerical value will light without flash.
4.6.5 Frequency Converter Mode Setting 1. CUCF mode only can be set in STDBY mode. In STDBY mode, enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the inquiring key ( ) for more than half a second(less than 2 seconds), select the function setting, choose battery voltage setting interface, at the moment, the letters “CF”...
4.6.6 Output Frequency Setting in CUCF Mode 1. Output frequency only can be set when CUCF mode is ON. 2. In STDBY mode, enter the setting interface. Press and hold the function setting key more than 2 seconds, then come to setting interface, Press and hold the inquiring key ( ) for more than half a second(less than 2 seconds), select the function setting, choose battery voltage setting interface, at the moment, the letters “OPF”...
secon nds), select the numeric cal value. Th he provided ID numbers s are 1, 2, 3, 4, 5, 6, 7, 8, you can choo se anyone b by yourself ( (The default t value is 1). 3. Conf firm the out tput voltage setting inte erface.
Page 30
(when d disconnect lo oad, it is a n ormal phen omenon to s show a sma all numerical l value of W WATT and VA). Temper rature: Dis splay the m maximum te emperature of the com mponents i in the UPS .
Press and hold the inquiring key for more than 2 seconds, LCD begins to display the items circularly and orderly which transfer to another every 2 seconds. Press and hold the key for some time again within 30s, it will return to output status. 5 WORKING MODE INTRODUCTION 5.1 Bypass Mode LED indications on front panel in bypass mode are as following:...
When th he mains po wer is low o or unstable, UPS will tur rn to battery y mode at on nce. 5.4 ECO O Mode LED ind dications on front panel in ECO mod de are as foll lowing: both h the inverte er green LED D and...
to make the buzzer stop beeping temporarily to wait for maintenance. You can also press the OFF key to shut down the UPS when confirmed that there is no serious fault. 6 THE WARNING CODE LIST OF THE LED LIGHT and DISPLAY PANEL Appendix 1: The table of the fault code Fault code...
Page 34
Appendix 2: Table for working status LED on Front panel Working status Alarm beep Note Normal Battery Bypass Fault Inverter mode (mains power) Mains power voltage ● Mains power high/low voltage protection, One beep / 4 sec ● ● ★ switch to battery mode Battery mode...
Page 35
overload Protect operation for Long beep ● ● ● battery mode overload Warning for bypass One beep / 2 sec ● ★ mode overload Fans fault(fan icon) One beep / 2 sec ▲ ▲ ▲ ★ Faults mode Long beep ●...
7 TR ROUBL LE SHO OOTING When th he system ru uns in failur e mode, the LCD will sh how as below Fault icon Fault c code Explicit t Troublesh hoot Introd uction Shee Trou uble indicat tion Failu ure point olution Fault LED on...
Page 37
Turn of the UPS and disconnect all the Fault LED on, audible buzzer load, make sure there no any fault or Persistently alarm, the fault code Output short-circuited internal short circuit of the load. is 45-49 And then restart the UPS, if failure still, please contact the supplier.
Page 38
IPP setting Attention: When the output is short-circuited, the action of the protection of the UPS will show up. Before turning off the UPS, please make sure to disconnect the entire load and cut off the AC mains power supply, otherwise will make the AC input short-circuit. Appendix 1: EMC Level The series product is designed to meet the below standard.
Page 39
Appendix 3: Specification Sheet MODEL SE906II SE9010II SE9015II SE9020II Capacity 6KVA/5.4KW 10KVA/9KW 15KVA/13.5KW 20KVA/18KW INPUT 3/1: 360V/365V/380V/400V/415VAC; Rated Voltage 1/1: 208V/210V/220V/230V/240VAC. (Set up by LCD display) 3/1: Half load (190-520)±5VAC, Full load (277-520)±5VAC; Voltage Range 1/1: Half load (110-300)±5VAC, Full load (160-300)±5VAC. Frequency 40-70Hz±0.5% (Auto sensing) 3/1: ≥0.95;...
Page 40
Typical Recharge Time 8 hours recover to 90% capacity ALARM Utility Failure Beep/4s Battery Low Beep/1s Overload Beep Twice/1s UPS Fault Long Beep ENVIRONMENT Humidity 20~90% RH @ 0~40 (non-condensing) Noise Level ≤58dB (1m) ≤60dB (1m) MANAGEMENT Standard RS-232 and USB Supports Windows 98/2000/2003/XP/Vista/2008/7/8 Optional SNMP Power management from SNMP manager and web browser...
8 GUARANTEE 8.1 Terms of Guarantee Our products are under a two-year guarantee starting from the date of delivery against malfunctions resulting from production, material and workmanship faults. Malfunctions due to such type of faults will be removed without claiming any price of workmanship or spare parts to be replaced.
MAKELSAN according to the direction to be made by the MAKELSAN head office. For malfunctions in the scope of guarantee, shipment fees are under the responsibility of MAKELSAN on the condition that products are delivered to the contracted freight company.
Page 43
Damages and breakdowns resulting from treatments, internally or externally tampering, efforts to repair and spare part replacement of products, without approval of MAKELSAN, those resulting from...