6-6 Communication function [option]
1) Function
· Data can be written/read through the MODBUS
2) Before using this function, please set related parameters as shown below.
3rd block parameter
PV
SV
Set the station No. at "STno"
(station No. setting paramter).
[Sample: station No. = 18]
3) Caution
· Station No. can be set in the range of 0 to 255. (No communication is allowed with 0).
· After changing the setting of parity at "COM", please power off and re-start the controller.
· Baud rate is fixed to 9600 bps.
®
protocol.
PV
SV
Set the parity at "COM".
CoM
0
Odd
1
Even
2
No parity
[Sample: Odd parity]
– 22 –
PV
SV
Please do not change "PYP"
unless used with PYP,
Color Touch-Operation Unit.