3. Installation (up to 4 dampers)
3.1 Power supply to master unit
Provide 230 V power supply to master unit.
L N
230V AC
Fuse 6,3A
L
N
G

3.2 Connect local fire dampers (up to 4)

Connect local fire dampers power supply and position switches to master unit.
Maximum 4 fire dampers could be connected directly to the master unit (FDS-M).
G0
D01
G0
D02
Fire damper's cables
1
2
Fire damper 2
1
Ceiling smoke detector
+
-
+
-
+
-
2,2 k
L1in
L2
L1out
0
230V
0
24V
Attention!
Color cables could change depending on motor
version. Numbering cables (1-2 for supply 24V, 1
to 6 for switches) stays the same on all motor ver-
sions.
Slave unit
G
G0
3.2
G0
D03
G0
D04
3.3
2
+
-
Smoke detector
3.2
B
A
Master unit
3.4
3.3
A
B
3.1
FDS-M
Fire damper 1
FDS-M
3.1
Duct smoke detector
FDS-M
FDS-M
+
-
+
Smoke detector
2,2 k
FDS-M
1
2
3
4
5
Fire damper 1
FDS-M
Smoke detector
2018-08-01
Power supply
- no slave unit
FDS-M
L
FDS-M
G0
Fire damper 1
1
+C
S2_1
S6_1
Fire damper 2
Ceiling smoke detector
S1
S4
S2
S6
Fire damper 2
+
-
L
N
G
-
+
-
+
-
1
2
2,2 k
SERVOMOTOR SWITCHES
L1in
L2
L1out
G0
D01
Power supply
0
1
2
Fire damper 2
Ceiling smoke detector
+
-
+
-
+
Slave unit
SERVOMOTORS
2,2 k
L1in
L2
L1out
0
230V
N
G
D01
G0
D02
2
+C
S2_2
S6_2
1
2
+
-
+
-
+
S1
S4
S2
S6
3
4
G0
D02
G0
D03
230V
0
24V
1
2
-
+
-
\ SEF
G
G0
Smoke detector
0
24V
B
A
Master unit
G0
D03
+C
S2_3 S6_3
-
Sm
G0
D04
B
A
FDS-M
A
B
7
1
2