6.5.9 Miscellaneous

Miscellaneous
NOTE
DO5 is for the interaction with AHU.
If using FDS-B (NC contact), set DO5 status on NC.
If other relay (NO contact) is used, set DO5 status on NO.
DO6-DO7 contact set depending on logic of the system.
26
I/O
Damper Durat. times
Detector values
In order to change sensitivity of smoke detectors
2018-08-01
DO5
Status:
NO/NC
DO6
Status:
NO/NC
DO7
Status:
NO/NC
EXT1
Status:
NO/NC
EXT2
Status:
NO/NC
Max durat. time:
Opening:
180
sec
Closing:
60
sec
OK
Detector Limits
High:
9.5
V
Smoke:
6.0
V
Dirty:
4.0
V
OK
OK
OK
Save current times
as orig. times?
Confirm:
NO
OK
Synch. parameters
Synchronize:
NO
Confirm
:
NO
OK