Description Of The System - Lindab FDS-M User Manual

Fire damper steering system
Table of Contents

Advertisement

1. Description of the system

The Fire Damper System (FDS) allows to feed, monitor and test up to 60 fire dampers. Smoke detectors can be con-
nected and monitored, as well. The system is designed to feed only 24V fire dampers.
The system is composed of:
FDS-M
FDS-S
Master
Slave
unit
unit
230 V
Communication (2 input)
24 V (2 input)
Communication + 24 V (4 input)
1 FDS-P
10 FDS-S
10 WH/WK
10 FDS-CD/DD
Fig. 1. FDS - Operating diagram
FDS-P
FDS-R
Power
Signal
supply
repeater
FDS-RB
FDS-DD
Relay
Smoke detectors
module
FDS-M
Master unit
4 fire dampers
4 smoke detectors
can be connected locally
to the master unit.
2018-08-01
FDS-CD
WH
Fire dampers
If
the
communication
cable is more than 300 m,
a signal repeater, FDS-R,
is required This is also
required if the number of
FDS-S exceeds 30.
WK
FDS-R
Signal
repeater
3