13.1 Updating the software

13.1.1 Main control and touch display

Updating can only be done via the web interface. Registration is done as described in sec-
tion
8.3.4.1
Start.
Click on Tools >> and then Update. In order to update the main control, enter the file name
and path in the input field and click "load". Alternatively you can select the file by clicking
the "Search..." button next to the input field.
After you clicked the "load" button the inscription "the update is being transfer to the con-
troller" appears. Wait until the update file is transferred and the AST11 is started anew.
"Updating Main Unit" appears on the display of the sequence controller AST11.
The update is completed when the main screen with the process display is displayed on
the display.

13.1.2 Power element

Updating can only be done via the web interface. Registration is done as described in sec-
tion
8.3.4.1
Start.
Click on Tools >> and then Update. In order to update the power element, enter the file
name and path in the input field and click "Load". Alternatively you can select the file by
clicking the "Search..." button next to the input field.
After you clicked the "Load" button the inscription "the update is being uploaded to the
controller" appears. Wait until the update file is transferred and the sequence controller is
started anew. "Updating Power Unit" appears on the display of the AST11.
The update is completed when the main screen with the process display is displayed on
the display.

13.2 Replace the filter mat of the sequence controller

Danger
Risk of fatal injury due to electrocution!
The work must only be performed by a licensed electrician!
The sequence of the work process must be adhered to!
Prior to opening the housing, the sequence controller must be switched
off and the power plug must be disconnected and secured against unau-
thorized plugging in!
Important
The filter at the sequence controller must be replaced in regular intervals
depending on the degree of contamination. The material used must meet
protective class IP54. Suitable filter mats are available under the order
number 826057.
All screwdriving connection described in the following work steps are
loosened or bolted using a hexagon socket wrench SW 2.5.