Compact Series Product Overview
Supported Point Types
Point Type
Analog
Voltage 0 to 10 Vdc
Input
4
Current 4 to 20 mA
RTD Pt 1K
1
RTD Ni 1K
2
Thermistor 10K NTC
Thermistor 100K NTC
Digital
Status (Binary Input)
Input
Pulse Accumulator
(Counter)
Analog
Voltage 0 to 10 Vdc
Output
Digital
Binary/Digital Output
Output
Platinum 1K 375 or 385 alpha.
1)
Siemens, Johnson Controls, and DIN Standard Nickel.
2)
10K and 100K Type 2 and 10K Type 3.
3)
Sensor supply 24 Vdc, 4.8W
4)
Point Type
Analog
Voltage 0 to 10 Vdc
Input
5
Current 4 to 20 mA
RTD Pt 1K
1
RTD Ni 1K
2
Thermistor 10K NTC
Thermistor 100K NTC
Digital
Status (Binary Input)
Input
Pulse Accumulator
(Counter)
12 | 100
Siemens Industry, Inc.
Building Technologies
Supported Point Types
The PXC Compact Series provides software-configurable and dedicated points. The
point types and their possible configurations are shown in the following tables.
PXC-16 Supported Point Types.
Configurable Points
Universal
Universal
Input (UI)
Input/Output (U)
Points 1-3
Points 4-8
•
•
•
•
•
3
•
3
•
•
PXC-24 Supported Point Types.
Configurable Points
Universal
Universal
Input (UI)
Input/Output (U)
Points 1-3
Points 4-12
•
•
•
•
•
3
•
3
•
•
Technical Reference Manual
Analog Output
(AO)
Points 9-11
•
•
•
•
•
•
•
•
•
•
Super Universal (X)
Points 13-16
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Restricted
Dedicated Points
Digital Input (DI)
Digital Output
Points 12-13
(DO)
Points 14-16
•
•
Dedicated Points
Analog Output
Digital Output
(AO)
(DO)
Points 17-19
Points 20-24
145-172